INSTALLATION, OPERATION

AND MAINTENANCE GUIDE

WATER CASSETTES

FIXING THE PANEL

After installation of the unit, mount the grille using the 4 screws provided

(fig. 12).

!

 

N.B.: It is very important to fix the grille in the right position

for  correct  connection  of  the  receiver  panel  to  the  unit.

Fig. 12

Use a spirit level  (fig. 10) to make sure that the unit is level and check

that it is securely fixed to the ceiling. In high humidity environments,

metal supports must be insulated using adhesive insulating material.

Fig. 11

To fix the unit to the ceiling, use the threaded bar and suitable screw

anchors as shown in fig. 09 (material not included in the supply).

C

B

D

A

Fig. 10

Fig. 07

        

 

 ATTENTION!

Catch up the cassette on the four

corners. Don't lift or move the unit

through the exchanger pipelines or

the  exhaust  pipe  condense.

!

-  to fix the panel only use the four supplied screws. Do not use other

kinds of screws or you could damage the condensate drain pan.

- Do not bend or narrow the unit piping.

- Do not remove the cap from the unit piping until immediately before

connecting the pipes.

- To prevent deformation of the air intake grille, do not overtighten the

screws.

CHANGE OF AIR AND RECIRCULATION SYSTEM

- Side knockouts allow connection of a duct for fresh air intake and for

conditioning an adjacent room.

- Remove the external prepunched anti-condensate insulator and

remove the knockout panels using a punch.

FRESH AIR RENEWAL

Remove  the  polystyrene  partition  and  insert  the  baffle  plate.

Use material purchased locally that is suitable for continuous operation

with temperatures of 60°C. The ducts may be in flexible polyester (with

steel spiral core) or in corrugated aluminium lagged with anti-condensate

material (fibreglass 12±25 mm thick). Upon completion of installation,

surfaces  that  have  not  been  insulated  may  be  covered  with  anti-

condensate insulating material (e.g.: 6 mm thick expanded neoprene).

Failure to comply with these instructions could cause dripping due

to the condensate; the manufacturer cannot be held responsible

for any damage. 

Any additional fan for external air intake (installer's

responsibility) must be connected to the terminal block as per the

enclosed  diagrams.  Fan  operation  is  in  parallel  to  the  damper

(electrothermal control valve), so that it stops when the valve closes.

Install an air inlet grille on the outside, with an inspectable filter holding

frame to prevent the entry of dust and leaves, which could irreparably

obstruct the unit heat exchanger coil.

RECEIVING, STORE AND MOVING THE UNITS

At the moment of the delivery of the unit, make sure that it corresponds

to the one indicated on the  transport document. Check the integrity of

the packing and the unit. Should there be any differences with the original

order or any damages, anomalies, or incomplete supply, please point

it out on the delivery note and inform the firm straight away. Never install

or use damaged apparatuses. The unit can be stored in room protected

from bad weather with temperature between the -20°C and the +55°C.

Transport the packed unit near as  possible to the installation place. To

avoid any damage to the unit, the plastic part (frontal panel and grille)

are furnished separately. The handling and the installation could be

facilitated cy use of an elevator(fig. 07).

INSTALLATION ACCESSORIES

n. 1 Cardboard mounting template;

n. 2 Batteries;

n. 1 Remote control;

n. 1 Auxiliary drain pan;

SELECTION OF CASSETTE INSTALLATION LOCATION

!

 

RECCOMENDATION!!

- The  unit  must  be  installed  in  a  solid  and  vibration-free  ceiling.

- There should be no obstruction of the air flow into and out of the unit

and the air should be evenly distributed throughout the whole room.

- Do not install the unit near sources of heat, steam or inflammable

gases.

- Install the unit near an electric socket or connect it directly to the

power supply.

- Do not install the unit in a place, which is exposed to direct sunlight.

- The selected place should allow easy drainage of the condensed

water.

- Periodically check appliance operation and leave sufficient space for

maintenance  around  the  appliance,  as  shown  in  the  figure  08.

- Install the unit so that the filter is easily accessible.

INSTALLATION

FIXING THE CASSETTE

Select a place of installation where there can be a clearance of a least

100 cm (see fig. 07) around the appliance. Make sure that the installation

does not interfere with existing electric wiring or plumbing. Establish the

position and size of the hole in the ceiling using the external diameter

of the cardboard mounting template (fig. 08).

>100

100 < H > 350

Fig. 08

Fig. 09

 Select the final position of the unit in the ceiling using the references

printed  on  the  cardboard  mounting  template  (fig.  09).

8

All manuals and user guides at all-guides.com

Содержание CSF Series

Страница 1: ...INSTALLATION USE AND MAINTENANCE MANUAL 0706 6180666 rev 0 GB CSF Series WATER CASSETTES All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 2: ...ndard water connection to heating cooling system 9 INSTALLATION OF AUXILIARY CONDENSATE DRAIN PAN 9 10 CONDENSATE DRAINAGE 10 ELECTRIC CONNECTIONS 10 Acces to the swhitchboard 10 Wiring diagram of 2 pipe system I R remote control 11 Wiring diagram of 4 pipe system I R remote control 11 Wiring diagram of 2 pipe system wall mounted control CD2 X7 12 Wiring diagram of 4 pipe system wall mounted contr...

Страница 3: ...of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room Ø A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80 Fresh air intake Ø D mm 65 65 65 65 Fresh air intake BxH E mm 120x80 120x80 120x80 120x80 B mm 225 225 225 225 180 325 325 325 X mm 65 5 65 5 65 5 65 5 70 73 73 73 Y mm 55 5 55 5 55 55 5 75 68 68 68 W mm 100 1...

Страница 4: ...m 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room Ø A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80 Fresh air intake Ø D mm 65 65 65 65 Fresh air intake BxH E mm 120x80 120x80 120x80 120x80 B mm 225 225 225 225 180 325 325 325 X mm 65 5 65 5 65 5 65 5 86 73 73 73 Y mm...

Страница 5: ...7 103 8 836 9 302 11 052 13 198 17 147 kPa 17 4 22 1 34 0 42 7 28 8 28 1 30 6 44 2 m c a 1 74 2 21 3 4 4 27 2 88 2 81 3 06 4 42 l h 391 550 709 882 928 1 103 1 317 1 711 l s 0 108 0 153 0 197 0 245 0 258 0 306 0 366 0 475 m3 h 543 611 680 815 832 1087 1087 1274 m3 s 0 151 0 170 0 189 0 226 0 231 0 302 0 302 0 354 g min 700 785 830 1100 540 610 610 630 dB A 51 53 57 62 54 58 58 62 W 58 126 126 124 ...

Страница 6: ... 340 kcal h 1 966 2 543 3 759 4 578 5 931 7 310 8 716 10 638 kPa 33 2 31 4 36 8 42 8 38 4 24 0 32 0 43 8 m c a 3 32 3 14 3 68 4 28 3 84 2 4 3 2 4 38 l h 196 254 375 457 592 730 870 1 062 l s 0 054 0 071 0 104 0 127 0 164 0 203 0 242 0 295 m3 h 543 611 680 815 832 1087 1087 1274 m3 s 0 151 0 170 0 189 0 226 0 231 0 302 0 302 0 354 g min 700 785 830 1100 540 610 610 630 dB A 51 53 57 62 54 58 58 62 ...

Страница 7: ...EC 73 23 and electromagnetic compatibly EEC 89 336 directives The installation should be carried out by a qualified installer Follow all current national safety code requirements In particular ensure that a properly sized and connected ground wire is in place Check that the voltage and frequency of the mains power supply are as required for the unit to be installed the available power source must ...

Страница 8: ...o that it stops when the valve closes Install an air inlet grille on the outside with an inspectable filter holding frame to prevent the entry of dust and leaves which could irreparably obstruct the unit heat exchanger coil RECEIVING STORE AND MOVING THE UNITS At the moment of the delivery of the unit make sure that it corresponds to the one indicated on the transport document Check the integrity ...

Страница 9: ...o stop the flow of water in the event of pump failure Fig 13 A B C Fig 16 2 50 A few examples are shown schematically below of condensate drainage connection in a correct fig 20 21 and incorrect manner fig 22 23 Fig 19 200 mm Fig 17 Fig 20 CORRECT E D F Fig 15 3 way motor operated valve Water inlet Tap Tap Water outlet AIR SUPPLY TO AN ADJACENT ROOM Remove the polystyrene taking care not to damage...

Страница 10: ...d be fitted with at least a switch isolator in conformity with European standard EN60947 3 Make sure that the electrical system is suitable for providing not only the working current required by the appliance but also the necessary current for powering household and other electrical appliances already in use Any electrical and mechanical alterations or tampering render the warranty null and void T...

Страница 11: ... red blue black yellow green brown M1 1 white red blue black yellow green brown WIRING DIAGRAM OF 4 PIPE SYSTEM WATER CASSETTE WITH I R CSF 41 44 ST CSF 45 48 LT L N brown red red red red red red blue yellow black red black black yellow black red Electricalsupply 230Vac 50 Hz L N C1 Cool valve 230Vac 50 Hz Earth relay 9 relay 4 relay 6 relay 2 relay 1 relay 3 P23 P18 P19 P20 P26 P27 P25 P24 P13 P1...

Страница 12: ...MP SW LV HR MIN START STOP SLEEP MODE FAN H TEMP COOL SLEEP SLEEP CLOCK START STOP LS1 NO NC red red blue black black M1 1 white yellow green white red blue black brown white red blue black yellow green brown red red blue black black M1 1 white yellow green bianco red blue black brown white red blue black yellow green brown nero LEGENDA Connector Earth L Phase N Neutral Com Common M1 Fan motor 230...

Страница 13: ...conditioner to come into contact with water The electrical insulation could be damaged with consequent possible risk of electrocution Check installation conditions in order to identify possible damage After prolonged use apply to specialised service personnel to control the installation conditions of the air conditioner Do not use flammable gas near the air conditioner Always use the appliance wit...

Страница 14: ...and to set a temperature which is lower than the room temperature For example if there is a temperature of 28 C in the room a temperature lower than 27 C should be set in order for the compressor and cooling to start The appliance automatically adjusts operating cycles in order to keep the room at the required temperature Upon completion of settings press the SEND button and listen for the beep to...

Страница 15: ...own in the drawing to the side The SLEEP mode automatically adjusts the temperature to make the sleeping environment more comfortable during the night During the cooling or dehumidifying modes the set temperature is increased gradually by 2 C during the first two hours of operation During the heating mode the set temperature is decreased gradually by 2 C during the first 2 hours of operation Timed...

Страница 16: ...amaged or not connected 5 TIMER indicator light blinks intermittently fig 44 B the filters must be cleaned When the cassette has been operating for more than 500 hours a warning is displayed as a reminder to clean the filter N B Reset by cutting off the power for at least 10 seconds CONDENSATE DRAIN PUMP OPERATION SPECIFICATIONS Cool Unit in operation the pump operates continuously until the set t...

Страница 17: ...button to start stop louver swing Louver direction adjustment optional Press the LV button to change the angle of the louvers which are controlled by the louver motor if the button is pressed and released the angle of the louvers is changed very slightly if the button is pressed and held the angle of the louvers continues to change until the button is released SLEEP Press the SLEEP button to start...

Страница 18: ...off the automatic circuit breaker TROUBLESHOOTTING 1 If the appliance does not switch on check that the mains supply is reaching the unit that the plug is properly inserted if the circuit breaker has tripped if there been a failure in the mains supply 2 If the cooling or heating effect seems less than normal check that the temperature has been set correctly if a window or door has been opened the ...

Страница 19: ...INSTALLATION OPERATION AND MAINTENANCE GUIDE WATER CASSETTES 19 All manuals and user guides at all guides com ...

Страница 20: ... the modifications considered necessary for improving the product at any time FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 806311 Fax 0429 806340 E mail info fastaer com http www fastaer com 0706 6180666 rev 0 All manuals and user guides at all guides com ...

Отзывы: