DEVICE PROGRAMMING UNIT USER’S MANUAL
| CHAPTER 2
16
PROGRAMMING
•
If the device was not programmed correctly, the
display will appear similar to the following:
8802 N/O ALARM
LOOP=1 ADDRESS=41
PROGRAMMING FAILED
<EXIT RE-DO>
Press EXIT to return to the Main Menu. Press RE-DO
to reprogram the detector.
When the device is disconnected from the 8720, the
display will go into search mode and display INSERT/
CONNECT).
8803
The 8803 must be programmed using cable P/N 555-
133891 that is stored in the cable compartment in the
bottom of the 8720. Before starting to program the
8803, open the cable compartment and insert the
programming plug in one end of the cable into the red
and black banana jacks in the cable compartment of the
unit. (Refer to Figure 2, pages 10-11.) Then follow the
procedure below:
•
With the 8720 displaying the Main Menu, press the
PROGRAM button. The 8720 will prompt the user to
insert or connect a device or detector.
•
Connect the device programming cable to the
device to be programmed. (Refer to Figure 2, pages
10-11.) When the 8720 has detected the device, the
display will appear similar to the following:
8803 AL/AL NO/NO
LOOP=1 ADDRESS=41
<LOOP ADDRESS>
<EXIT PROGRAM>
The top line indicates the device type, the contact
state of the input and the device usage. The next
firealarmresources.com
Содержание 8720
Страница 2: ...firealarmresources com...
Страница 4: ...DEVICE PROGRAMMING UNIT USERS MANUAL CONTENTS ii TABLE OF CONTENTS firealarmresources com...
Страница 22: ...DEVICE PROGRAMMING UNIT USER S MANUAL CHAPTER 2 18 PROGRAMMING firealarmresources com...
Страница 35: ...firealarmresources com...
Страница 36: ...P N 315 033260FA 3 8 Fernwood Road Florham Park New Jersey 07932 firealarmresources com...