IV - 1
The 15208 Troubleshooting Module is used to
aid in locating any main board troubles except
zone troubles. The following steps should be
used.
Step 1.)
Disconnect all power into
system, including batteries.
Step 2.)
Remove L.E.D. indicator mask
from main board.
Step 3.)
Plug module into connector
J2, as shown.
Step 4.)
Apply power to system.
Step 5.)
Locate activated trouble indi
cator on 15208 module.
Step 6.)
Repair problem(s). If
problem can't be solved,
contact the factory for assis-
tance.
Step 7.)
Remove module.
Step 8.)
Replace L.E.D. indicator mask
on main board.
TROUBLESHOOTING GUIDE
CAUTION:
Fire alarm system troubleshooting and repairs are to be done
only by qualified service technicians
L.E.D. DESCRIPTIONS
MODULE MOUNTING DIAGRAM
444775
firealarmresources.com