III-
3
14048 BATTERY SET MOUNTING AND
WIRING DIAGRAM
14047 BATTERY SET MOUNTING AND
WIRING DIAGRAM
RESISTOR COLOR CODES
Step 4.)
Reinstall the main board as originally installed.
Step 5.)
Connect the primary (main) power supply wires
to the control unit.
Step 6.)
Apply power to system. The following
indications must occur:
A.) System power L.E.D. on.
B.) System trouble L.E.D. flashing.
C.) Trouble buzzer pulsating.
D.) All zone trouble L.E.D.s on.
NOTE: The trouble buzzer can be silenced by
putting the trouble silence switch in the
silenced position.
Step 7.)
Remove power from system.
Step 8.)
To check the supervised circuits of the Control
unit:
A.) Place two 47K ohm resistors (P/N 942666)
across signal circuit terminal 1 and 2.
B.) Place a 3.9K ohm resistor (P/N 942665)
across each initiating circuit, terminals 1
and 2.
WARNING: Improper battery connections or shorting
battery terminals may damage the panel
and/or batteries and may cause personal
injuries.
C.) If a 14047 or 14048 battery set is used:
1.) Place the batteries in the space provided
in the bottom of the backbox.
2.) Use crimp-on receptacles (P/N J010575)
to connect batteries in series with
#18 AWG wire.
3.) Plug the black "B-" lead from the control
unit into the black or "-" terminal of the
battery set and plug the red "B+" lead
from the control unit into the red or "+"
terminal of the battery set.
firealarmresources.com
Содержание 15220A
Страница 10: ...firealarmresources com...
Страница 21: ...III 6 BACKBOX DIMENSIONS firealarmresources com...
Страница 22: ...III 7 SEMI FLUSH MOUNTING DIAGRAM firealarmresources com...