Parts Supplied
1
15207
Supervisory Module
1
444832
Instruction Sheet
INSTALLATION INSTRUCTIONS FOR
CAT. NO. 15207 SUPERVISORY MODULE
The 15207 Supervisory Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control
Unit. This module provides a separate, audible indication of a supervisory condition in Zone #1 of the Control
Unit. When Zone #1 is programmed for supervisory, (See Owners Manual Pg. #III-5), the supervisory silence
switch can be operated to silence the audible signal and light the supervisory silenced L.E.D. After supervisory
condition is cleared, the buzzer will sound again until the switch is returned to its normal position. This module
contains a yellow silenced L.E.D., a buzzer for audible supervisory condition indication, and a supervisory
condition silence switch.
Cat. No. 15207
Supervisory Module
Cat. No. 15207
Supervisory Module
Step 1.)
Installation is to be done only by qualified
personnel who have thoroughly read and
understood this instruction sheet.
Step 2.)
Disconnect all power into system,
including batteries.
Step 3.)
Remove L.E.D. indicator mask from main
board. Remove lower left screw holding
main board in place.
Step 4.)
Install module onto main board.
A.) Place module onto connector J5
taking care to maintain orientation
as shown.
B.) Attach bracket to main board using
screw removed in Step 3.
C.) Diodes D5, D27, D30 and D31 on
main board must be cut out of main
board.
Step 5.)
Apply power to system.
Step 6.)
Check for proper operation of module
functions.
Step 7.)
Replace L.E.D. indicator mask on main
board.
444832 - Rev. A