III-
41
Step 1.)
Installation is to be done only by qualified personnel who
have thoroughly read and understood this instruction
sheet.
Step 2.)
Disconnect all power into system, including batteries.
Step 3.)
Program the module for the type of alarm output needed
for city tie.
A.) Remote station transmitter (reverse polarity).
1.) Cutout resistor R4.
2.) Connect jumpers across W1 and W3 pin
terminals.
3.) Go to step #4.
B.) Local energy city box.
1.) Connect jumpers across W2 and W4 pin
terminals.
2.) Go to step #4.
C.) Not required at installation.
1.) Connect jumpers across W1 and W3 pin
terminals.
Step 4.)
Install module to left side of cabinet.
A.) Place four - #10-3/8" spacers (P/N P8397-11) over
studs on the left side of the cabinet.
B.) Mount module with terminal block towards front
cover.
C.) Use four - #6-32 keps nut (P/N 18965) to secure
module in place.
D.) Plug cable and connector ass'y (P/N 444466) into
the module connector J1 and main board
connector J4 with the colored rib on the dot at both
ends.
CAUTION: Check to see that the connectors are
properly seated on all of the pins.
Step 5.)
Connect field wires as required.
Step 6.)
Apply power to system.
Step 7.)
Check for proper operation of module functions.
The 15215 City Tie / Auxiliary Relay Module is an optional module for the 15220(A) or 15240(A) Fire Alarm
System Control Unit. This module provides a supervisory / trouble transmitter, an alarm / trouble transmitter or a
local energy city box trip circuit, a form "C" system trouble contact, and a form "C" general alarm contact. The
module also contains a city tie / relay disconnect switch and a yellow trouble / off-normal switch L.E.D. The
disconnect switch may be activated during testing or servicing of the system to prevent a supervisory or an alarm
output from this module (a trouble output will be generated upon activation of the disconnect switch).
Module Mounting Diagram
INSTALLATION INSTRUCTION AND WIRING FOR
CAT. NO. 15215 CITY TIE/AUXILIARY RELAY MODULE
444732 - Rev. A
Parts Supplied
1
15215
City Tie/Auxiliary
Relay Module
4
P8387-11 Spacer #10- 3/8"
4
18965
#6-32
Keps Nut
1
444466
Cable and Connector Ass'y
1
444732
Instruction Sheet
firealarmresources.com
Содержание 15220A
Страница 10: ...firealarmresources com...
Страница 21: ...III 6 BACKBOX DIMENSIONS firealarmresources com...
Страница 22: ...III 7 SEMI FLUSH MOUNTING DIAGRAM firealarmresources com...