III-
32
BATTERY SIZE CALCULATIONS
STANDBY
ALARM
CURRENT
CURRENT
(A.)
(A.)
CONTROL UNIT (2 ZONES)
.025
.110
ADD FOR A 4 ZONE CONTROL UNIT
+.010
+.080
OPTIONAL MODULES
15212 - REMOTE ANNUNCIATOR MODULE
+.002
+.050
7704 ANNUNCIATOR
+.022
+.092
15213A - MARCH TIME/TEMPORAL SIGNALING
+ 0
+.050
15219 - ZONE RELAY MODULE
+ 0
+.115
15209 - CITY TIE MODULE
+.001
+.035
15215 - CITY TIE/AUXILIARY RELAY MODULE
+.002
+.080
15217 - AUXILIARY RELAY MODULE
+.001
+.030
15207 - SUPERVISORY MODULE
+ 0
+ 0
15206 - D.A.C.T INTERFACE MODULE
+.002
+.045
2-WIRE SMOKE DETECTORS
CAT. # OF SM. DET.
QUANITY
X CURRENT (A.)
X
=
+
N/A
X
=
+
N/A
X
=
+
N/A
4-WIRE SMOKE DETECTORS
CAT. # OF SM. DET.
QUANITY X CURRENT (A.)
STANDBY
X
=
+
N/A
ALARM
X
=
N/A
+
STANDBY
X
=
+
N/A
ALARM
X
=
N/A
+
STANDBY
X
=
+
N/A
ALARM
X
=
N/A
+
STANDBY
X
=
+
N/A
ALARM
X
=
N/A
+
END OF LINE RELAY QUANITY
X CURRENT
X
=
+
+
CAT. # OF SIGNAL
QUANITY
X CURRENT
X
=
N/A
+
X
=
N/A
+
X
=
N/A
+
X
=
N/A
+
7700 TROUBLE UNIT
=
+.040
+.040
OTHER
=
+
+
TOTAL
TOTAL STANDBY CURRENT HOURS OF STANDBY REQUIRED PER
(FROM ABOVE)
N.F.P.A. STANDARD (24 OR 60)
A. X
HOURS
=
A.H. FOR
STANDBY
TOTAL ALARM CURRENT
5 MINUTES OF ALARM OPERATION
(FROM ABOVE)
PER N.F.P.A. STANDARD *
A. X
0.33
HOURS
=
A.H. FOR
ALARM
A.H. FOR S
A.H. FOR ALARM =
A.H. REQUIRED
BATTERY CAPACITY**
*
An additional multiplier is included to compensate for the higher discharge rate in alarm.
**
Battery capacity decreases with age, a four year old battery can lose up to 50% of its capacity.
Compensations should be made to allow for this loss.
NOTE:
The minimum battery size used should be 6 A.H. and the
maximum battery size is 15 A.H.
firealarmresources.com