4.15. General settings.
General settings establish some parameters that are necessary for the relay to operate.
These settings are defined as general because they affect the entire relay, and as a result
they are not subject to a change of table.
Function
Description
Minimum
Maximum
Step
Unit
Default
General Settings
Equipment identifier
-
-
-
-
“SIL-V”
Frequency
-
-
60/50
Hz
50
Serial number
-
-
-
-
0
Language
-
-
-
-
English
Active table
1
3
1
-
1
Connection type
(1*)
-
3VT (P-N) + Vr
Nominal voltage (phase-phase)
110
480
1
V
110
VT transformation ratio
1.0
3000.0
0.1
-
1
Local Modbus address
1
247
1
-
1
Remote address (*)
1
247
1
-
3
Remote baudrate (*)
4800
38400
-
bauds
19200
Remote protocol (*)
(2*)
IEC60870-5-103
(1*) 3VTs (P-N), 3VTs (P-N) + Vr, 3VT (P-P) + Vr, 3VT (P-P)+ Vbb, 2VTs (P-P) +Vr
(2*) Modbus RTU or IEC60870-5-103 only in SILVxxxxxA(E,I)xxxx models.
(*) Remote communication parameters depend on model (protocol options:IEC60870-5-103 or
Modbus RTU or IEC6185, DNP3.0 or IEC60870-5-104)
1.
Equipment Identifier
. This is an ASCII text, for equipment identification. Normally
protection equipment is associated with a specific line or position, and this setting is
used for this identification. It is important that this field is filled in correctly, as the
information regarding events and oscillography are accompanied with this information.
2.
Frequency
. It is possible to select the frequency by general settings
3.
Serial number
is a read only setting
4.
Language
. The SIL equipment is capable of displaying their messages in four
languages, with English in all cases. Consult the list of models to find out which are
available
5.
Active table
: see Settings Table.
Содержание SIL-V
Страница 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Страница 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Страница 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Страница 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Страница 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Страница 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Страница 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Страница 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Страница 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Страница 192: ...www fanox com Rev 10 192 212...
Страница 210: ...www fanox com Rev 10 210 212 12 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 211: ...www fanox com Rev 10 211 212 NOTES...
Страница 212: ...www fanox com Rev 10 212 212...