4.14.1. Syncronism (25) and manual closure (52)
For the manual closure of 52 function is supervised by the sync function, it is necessary to
associate the "Permission of closure " status of sync function to the logical signal "Manual
close enable” to the desired state of the synchronism function.
It is shown an example where the manual close is desired when there is synchronism
condition or the line and the bar are dead (DLDB).
CONFIGURATION:
•
Manual closure init
logical signal
one of the commands of
close breaker
(via
local HMI/SICom or via communications Modbus/IEC60870-5-103)
•
Manual closure enable
logical signal
synchronism
condition or
DLDB
condition
•
Physical output
(in this example output 3)
Manual closure
condition and
recloser
condition.
(in this case the output 3 should be connected to the closing coil of the circuit breaker)
Содержание SIL-V
Страница 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Страница 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Страница 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Страница 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Страница 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Страница 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Страница 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Страница 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Страница 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Страница 192: ...www fanox com Rev 10 192 212...
Страница 210: ...www fanox com Rev 10 210 212 12 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 211: ...www fanox com Rev 10 211 212 NOTES...
Страница 212: ...www fanox com Rev 10 212 212...