4.13. 79 Autorecloser
The reclosing function recloses the circuit breaker after a fault. It has a five reclosing
capacity, following which the unit shall be Locked or in “Lockout” mode.
The reclose device can be permitted or prohibited, depending on whether or not this
function is required. Prohibited must not be confused with locked. Prohibited means that
the recloser shall never be in operation, regardless of the controls performed on it. A
locked recloser means that the recloser is not operative, but either because it has reached
the end of the reclosing cycle, or a fault has been detected, or someone has performed a
control procedure on it.
There is a final permission which serves to indicate that recloser that it must wait a period
of time before closure. In this time, there is usually an external condition, such as closure
synchronism, and this condition in from an external input.
Each reclosing cycle has its own specific Operating time that can be set. Apart from these
times, a further three times must be set:
•
Hold times. This is the time the reclosing device waits for an external condition for
closure.
•
Replacement time. This is the Hold time for the recloser for a final closure. If during this
time, there is another trip, the recloser count will increase.
•
Final opening time The is the time used by the recloser to declare that the circuit
breaker is finally open. In this case, the recloser understands that the opening was
manual or via remote control, and no reclosing is necessary. On exceeding this time,
the recloser shall switch to locked mode.
The reclosing function settings are shown below:
Group
Description
Minimum
Maximum
Step
Unit
Default
79
Reclosing device
Permission
-
-
Yes/No
-
No
Hold permission
-
-
Yes/No
-
No
Number of reclosings
1
5
1
-
3
Reclose 1 time
0,02
300,00
0,01
s
0,30
Reclose 2 time
0,02
300,00
0,01
s
3,00
Reclose 3 time
0,02
300,00
0,01
s
180,00
Reclose 4 time
0,02
300,00
0,01
s
180,00
Reclose 5 time
0,02
300,00
0,01
s
180,00
Hold time
0,02
300,00
0,01
s
10,00
Reset time
0,02
300,00
0,01
s
10,00
Final Opening Time
0,02
300,00
0,01
s
10,00
Содержание SIL-V
Страница 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Страница 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Страница 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Страница 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Страница 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Страница 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Страница 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Страница 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Страница 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Страница 192: ...www fanox com Rev 10 192 212...
Страница 210: ...www fanox com Rev 10 210 212 12 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 211: ...www fanox com Rev 10 211 212 NOTES...
Страница 212: ...www fanox com Rev 10 212 212...