Rev.10
28/212
4.3.
Function 59. Definite-time phase overvoltage
There are two independent phase overvoltage functions
This protection function is adjusted using four parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
59_1
59_2
Definite-time phase overvoltage
Permission
-
-
Yes/No
-
No
Pickup
6,0
999,0
0,1
V
10,0
Operating time
0,02
300,0
0,01
s
1,00
Reset time
0,02
300,0
0,01
s
0,20
The operating time is completely independent from the measured phase voltage, such that
if the phase voltage exceeds the adjusted value for a period of time equal to or higher than
the pre-established value, the protection function actuates (trips) and does not reset itself
until the measured phase voltage value drops below the pre-established voltage point
during adjusting reset time.
The function activates at 100% of the adjusted input and deactivates at 95%. Reset is
temporized and reset time is adjusted with reset time parameter.
The accuracy of the operating time is the adjusted time ±30ms or ± 0.5% (greater of both).
4.4.
Function 59N. Definite-time neutral overvoltage
There are two independent neutral overvoltage functions
This protection function is adjusted using four parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
59N_1
59N_2
Definite-time neutral overvoltage
Permission
-
-
Yes/No
-
No
Pickup
6,0
999,0
0,1
V
10,0
Operating time
0,02
300,0
0,01
s
1,00
Reset time
0,02
300,00
0,01
s
0,20
The operating time is completely independent of the measured neutral voltage, such that
should the neutral voltage exceed the set value during the same amount of time or more
than the set one during Operating time, the protection function acts (trips) and there it is
not restored until the measured value of the neutral voltage drops below the voltage set
point during adjusting reset time.
The function pick up occurs at 100% of the adjusted input and the dropout at 95%. The
reset type is temporized and reset time is adjusted with reset time parameter.
The accuracy of the operating time is the adjusted time ±30ms or ± 0.5% (greater of both).
NOTE
: Depending on the configuration the neutral voltage can be measured or
calculated:
Содержание SIL-V
Страница 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Страница 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Страница 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Страница 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Страница 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Страница 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Страница 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Страница 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Страница 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Страница 192: ...www fanox com Rev 10 192 212...
Страница 210: ...www fanox com Rev 10 210 212 12 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 211: ...www fanox com Rev 10 211 212 NOTES...
Страница 212: ...www fanox com Rev 10 212 212...