![FANOX SIA C Series Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/fanox/sia-c-series/sia-c-series_installation-and-commissioning-manual_4588696025.webp)
ISO 9001:2008
www.fanox.com
SIAC116B1011AB_Rev. 05
25 / 32
Considering this description, the real thermal image that will support the relay depending on the
injection mode and injection system is shown below:
WAVE FORM
INJECTION MODE
THERMAL RESISTANCE
SINGLE PHASE P-N
3xIn continuously
20xIn during 10 seconds
70xIn during 1 seconds
3-PHASE BALANCED
3xIn continuously
20xIn during 10 seconds
70xIn during 1 seconds
3-PHASE
UNBALANCED
1xIn continuously
6.5xIn during 10 seconds
23 xIn during 1 seconds
NOTE:
It is checked that thermal image values are re-defined not to exceed the declared value
in the International Standard:
Commisioning recommendation:
•
It is recommended to use Kitcom accessory for relay protection functions settings.
Connect it for setting and disconnect it for testing purpose.
•
Adjust manually current generation value without injecting current to relay, for not
stressing it during adjustment process.
•
Be sure that relay output contact is connected to generator tripping input in order to stop
the generator, hence the current injection, after reaching adjusted tripping time. This
way, relay will only withstand rated injected current during adjusted time at protection
function settings, not maintaining current injection constantly, which could become a
damaging situation for relay, as in other case, the internally handle energy will be higher
than rated one.
•
Not to perform repetitive trips continuously as the stress of the relay will be increased
drastically, especially when high current is being injected on the relay.
By following these recommendations, relay should pass commissioning test successfully. If
commissioning test is performed not
following these recommendations, manufacturer won’t be
responsible for relay failure.