ISO 9001:2008
www.fanox.com
SIAC116B1011AB_Rev. 05
23 / 32
7.3.5. Demand menu
How to delete the demand
7.3.6. Fault reports menu
How to delete the fault reports
SIA-C relay provides the demand of current with the
following characteristics:
•
Number of records: 168
•
Recording mode circular
•
Sampling
rate
(interval):
configurable
through communications: 1
– 60 min
•
Record format:
Date/Time
IMAX (in interval)
IMAX (actual)
IA
IB
IC
IN
To delete the demand from the relay it is
necessary to insert the password 5555 from the
demand menu.
From the standby mode screen, press the “OK” key
to access the first line of menus. Use the “▲” and
“▼” keys to position the cursor over the “FAULT
REPORT
” screen. Press "OK" and use the “▲” and
“▼” keys to position the cursor over the faults.
Once it is accessed to a fault report, press “OK”, to
visualize the cause which has originated the fault
report.
Pressing “OK” again it is accessed to the registered
events that are related with that fault reports. The first
event is the activation of the fault report. To visualize
the rest events, use “▼” key.
To delete the fault reports from the relay it is
necessary to insert the password 5555 from the
fault report menu.