How to set Trip Voltage level
7.3.4. Events menu
How to delete the events
From the standby mode screen, press the “OK”
key to access the first line of menus. Use the “▲”
and “▼” keys to position the cursor over the
“EVENTS” screen and the number of events in the
buffer will be displayed. Press "OK" and use the
“▲” and “▼” keys to position the cursor over the
events.
The “┘” and “┐” shows the event has been caused
by the activation or reset.
Each event contains the following information:
Date-time; Description of the event
Size of the events buffer; Position of the
event within the list
Caused by activation or reset; Associated
measurement
To delete the events from the relay it is necessary
to insert the password 5555 from the events menu.
After the erasing of the events it will be
appear
there is
1 event corresponding to “Events erased
”
NOTE
: When the events are deleted, the faul
reports persist in the relay to analyze the fault
situation until these faults reports are deleted
consciously by the user
.
Pressing “OK” key from the standby screen it is
displayed MEASUREMENT menu.
Use “▼” key till SETTINGS menu appears. Pressing
“◄” key it is accessed to GENERAL settings.
Use “▼” key to overview the options and press “OK”
when “Trip Voltage level” option appears.
After inserting the password 5555 it will be possible
to select the desired value.