General settings
From the standby mode screen, press the “OK” key to
access the first line of me
nus. Use the “▲” and “▼” keys
to position the cursor over the “SETTINGS” screen. Press
the “◄” key to access the general settings from the
"SETTINGS" screen.
The general setting "Equipment name" can be viewed
from the HMI, but it can only be modified by using the
SICom program.
The value, of the "CT
Phase ratio” and “CT Neutral ratio”
general settings, is the result given by dividing the
number of turns on the primary winding by the number on
the secondary winding. For example: With CT 500/5, the
setting would be 100.
The frequency is selected for each model. The value is
read only.
How to set CT Phase ratio
Pressing “OK” key from the standby screen it is displayed
MEASUREMENT menu.
Use “▼” key till SETTINGS menu appears. Pressing “◄” key it is
accessed to GENERAL settings.
Use “▼” key to overview the options and press “OK” when “CT phase
ratio” option appears.
After inserting the password 5555 it will be possible to adjust the
wanted value.