Lumina 71
Alarm
47
15.1.2
Dealing with a SILENT alarm
If the alarm system is active and a SILENT alarm occurs, the LED near the alarm key will flash green. When the
alarm key has been pressed 1x the alarm screen will appear with the warning. Press alarm key 2x to remove the
warning from the screen.
15.1.3
An alarm recovers
With LOUD alarms the alarm situation can be recovered after a while by the user or the control computer.
In the event of a LOUD alarm, the siren will activate first (
Alarm status = ALARM
). If the value responsible for
causing the alarm comes within the alarm limits again, the situation is considered recovered and the alarm is over.
The siren automatically deactivates and the alarm status changes into
RECOVERED
. This message remains visible
so the user can see what caused the alarm. Press alarm key 2x to remove the message from the screen.
15.2
Deactivating the alarm system
The controller alarm can be fully deactivated. Do this e.g. when the house is empty. The controller will give a
warning to indicate that the entire alarm system has been deactivated.
If the alarm system is deactivated the control computer will not generate any alarm messages (except
system alarms). Never switch the alarm system off during regular operation.
Deactivate the alarm system as follows:
1. Press the alarm key.
2. Change the
Alarm system
status to
OFF
.
The screen shows that the alarm system has been deactivated. A corresponding alarm message will also
appear in the
Alarm overview
. The LED near the alarm key will flash green.
Reactivate the alarm system by changing the
Alarm system
to
ACTIVE
. The alarm message stating that the system
has been deactivated will be cleared from the
Alarm overview
.
15.3
Testing the alarm system
Test the alarm system as follows:
1. Press the alarm key.
2. Change the
Alarm system
status to
TEST
.
The control computer prepares an alarm message. This appears in the alarm overview and can be cleared by
pressing the alarm key. The status of the alarm system will immediately revert to
ACTIVE
.
Fancom advises testing the alarm system weekly for correct functioning. During the test the control
computer will give a loud alarm.
15.4
System alarms (ERROR nn)
The control computer also tests a number of functions of the control computer itself.
Always warn the installer if a system alarm occurs.