Lumina 750
Classic screens
6.10
Function key 9: Phase times
9
Start
Readout of the time the current phase was started by the Lumina 750.
End1
Setting of the earliest time the computer can switch to the next phase.
The Lumina 750 only calculates this end time in the phases: Levelling (1),
Pasteurization (3) and Cool down conditioning (4).
End2
Setting of the latest time the Lumina 750 can switch to the next phase.
The Lumina 750 calculates this end time during all the phases. If
the maximum phase time has not been entered, the computer will
automatically add one year to the current time and date and enter this as
the maximum phase time. This prevents the Lumina 750 switching to the
next phase prematurely.
The thermal control can also be used to control the pressure in a tunnel
by controlling anexhaust valve.
Phase
Readout of the time (days, hours and minutes) that has already elapsed in this
current phase.
Cycle
Readout of the time (days, hours and minutes) that has already elapsed in this
current cycle (from empty position).
Min.
Readout of the minimum time (days, hours and minutes) the Lumina 750 must
remain in the current phase.
This setting only applies to phases where the computer can switch
to the next phase earlier under certain circumstances: Levelling (1),
Pasteurization (3), Cool down conditioning (4) and Cool down cook out
(11).
Max.
Readout of the maximum time (days, hours and minutes) the Lumina 750 must
remain in the current phase. When this time has elapsed the computer will proceed
to the next phase. This only applies to phases where an automatic time based
switch is made to the next phase: Levelling (1), Pasteurization (3), Cool down
conditioning (4) and Cook out (10).