Lumina 750
Alarm
4.
Alarm
The Lumina 750 displays the alarm overview by pressing
. There are two types of alarm:
1.
Loud alarm
: An active loud alarm sounds a siren, shows an alarm message and a report on the screen. This
type of alarm has a
high priority
.
2.
Silent alarm
: An active silent alarm shows an alarm message and a report on the screen. This type of alarm
has a
low priority
.
4.1
Alarm overview
Status
Readout / setting the alarm status:
●
Alarm
: the type of alarm is presented on the display.
●
Alarm stand by
: no alarm is presented. The alarm is stand by.
●
Alarm test
: the alarm is tested. After the test the alarm will be reset and the
alarm status changes to
Alarm stand by
.
●
Alarm cancelled
: an alarm is cancelled. The control computer switches off the
alarm, but the alarm status remains visible.
●
Silent alarm
: an alarm message is presented on the display only.
●
Alarm temporary. off
: switch off the current alarm. When the alarm is been
cancelled the status will automatically change to
Alarm stand by
. Always check if
the status is reverted to
Alarm stand by
.
●
Alarm disabled
: switch off the alarm entirely. Perform this activity only if a room
(growing room / tunnel / bunker) is unoccupied. Do not forget to reset the alarm
status to
Alarm stand by
.
●
-
: alarm function is not in use.
Message
Readout of the alarms (see table below).
29