SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
Trip Code Descriptions
Fail Safe operation
2601-2699
Operation 2 Trip
A process associated with the Logging function has been affected and is unable to recover automatically
The trip can be reset by either the digital input or keypad or the bus command depending on the control method set.
It is also possible to reset this trip by cycling the control supply
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Fail Safe operation
2501-2599
Operation 1 Trip
A process associated with the Keypad board has been affected and is unable to recover automatically
The trip can be reset by either the digital input or keypad or the bus command depending on the control method set.
It is also possible to reset this trip by cycling the control supply
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Fail Safe operation
2401-2499
Operation 3 Trip
A process associated with the Control Board has been affected and is unable to recover automatically
The trip MUST be reset by either the digital input or keypad or the bus command depending on the control method set.
This trip is a special case and it is NOT possible to reset this trip by cycling the control supply
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Current sensor failure
2301-2303
Current Sensor Trip
One or more of the internal sensors used to measure current has failed or is reading a low value.
Check the connections to the supply and motor as disconnection will result in a zero current reading.
Check the plate FLA of the motor being controlled is at least 25% of the "i-motor" rating
The Trip Number shown in PNU Name is a
decimal value