SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0Degrees
-
55 ( 37 hex ) 55Degrees
Default
0 ( 0 hex ) 0Degrees
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
17000 ( 4268 hex ) 17A
-
2000000 ( 1E8480 hex ) 2000A
Default
17000 ( 4268 hex ) 17A
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
10 ( A hex ) Trip Class 10
-
30 ( 1E hex ) Trip Class 30
Default
10 ( A hex ) Trip Class 10
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range( 0.5 x PNU25600 ) 50% I-ratedA -
( 1 x PNU25600 ) 100% I-ratedA
Default ( 1 x PNU25600 ) 100% I-ratedA Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
17000 ( 4268 hex ) 17A
-
2000000 ( 1E8480 hex ) 2000A
Default
17000 ( 4268 hex ) 17A
Type
Read Only
25792 ( 64C0 hex )
Unit Class10 Current Rating
i-Synergy
32 bit unsigned
Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
25728 ( 6480 hex )
This should be set to the Full Load Current shown on the motor plate
Motor Current
The overload works with multiples of the set "Motor Current" (i-motor)
32 bit unsigned
Also referred to as Motor FLA
Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
25664 ( 6440 hex )
The trip class is a numeric value that correlates the trip time with overload level.
Select Trip class according to application requirements
Trip Class
The trip time depends on the selected Trip Class. The duration of the overload and the level of the over current.
Refer to the Motor Overload 'cold' trip curves given in the Quick Start Guide.
16 bit unsigned
When "Class 20" or "Class30" are selected the Unit current rating (i-Unit) will be reduced to a lower value (i-rated).
10= Trip Class 10, 20 = Trip Class 20, 30 =
Trip Class 30
25600 ( 6400 hex )
Unit Class20 / Class30 Current Rating
i-rated
32 bit unsigned
Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
23040 ( 5A00 hex )
The maximum possible Delay angle for the current iERS saving phase
BackStop
Displayed for diagnostic purposes
16 bit unsigned
May decrease during heavy load periods or instability
Linear Scaling (1 = 1° of mains cycle)
Time(ms)=(Value/PNU32000)*(25/9)
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 24 of 59