SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
20480 ( 5000 hex )
Automatically controls the maximum iERS saving level.
Automatic Impact Load
On : The maximum iERS saving level ("BackStop" ) is reset to maximum during each load cycle.
8 bit unsigned
Off : The saving potential may be reduced on applications with heavy load cycles. Such as injection moulding machines.
Binary value
20416 ( 4FC0 hex )
Automatically controls the "Stop Time"
Automatic End Stop
On : The ramp time is shortened if the motor reaches a very low speed before the end of the "Stop Time"
8 bit unsigned
Off: The ramp time " depends on the "Stop Time" and "Current Limit"
Binary value
20352 ( 4F80 hex )
Automatically controls the torque applied to the motor during the soft start.
Automatic Ramp
On : The torque is adjusted to suit the load.
8 bit unsigned
Off: The ramp time depends on the "Start Time" and "Current Limit"
Binary value
20224 ( 4F00 hex )
Automatically controls the soft stop to eliminate oscillations that can occur towards the end of the ramp
Auto Smooth Stop
On : The soft stop is adjusted when oscillations are detected. Refer to "Auto smoothing Level"
8 bit unsigned
Off : The soft stop is unadjusted and torque fluctuations may cause instability. This can often occur in pumping applications
Binary value
20160 ( 4EC0 hex )
Automatically controls the soft stop to suit the application.
This feature is particularly useful with pumping applications
Automatic Stop
On : If the motor is lightly loaded it decelerates rapidly to the point where the soft stop becomes useful.
8 bit unsigned
Off : The deceleration to the point where the soft stop becomes useful will be slower.
Binary value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 21 of 59