SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
7872 ( 1EC0 hex ) -20°C
-
1280 ( 500 hex ) 80°C
Default
Not Applicable °C
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
7872 ( 1EC0 hex ) -20°C
-
1280 ( 500 hex ) 80°C
Default
Not Applicable °C
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
7872 ( 1EC0 hex ) -20°C
-
1280 ( 500 hex ) 80°C
Default
Not Applicable °C
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read Only
40321 ( 9D81 hex )
Displays the overload level at the end of the last successful start -1
Last overload-1
16 bit unsigned
Linear Scaling ( 1 = 0.006104 % )
40320 ( 9D80 hex )
Displays the overload level at the end of the last successful start
Last overload
16 bit unsigned
Linear Scaling ( 1 = 0.006104 % )
39689 ( 9B09 hex )
Displays the heatsink temperature at the end of the last successful start-9
Last temperature -9
16 bit (Highbyte=b11-b8, LowByte=b7-b0)
Ta >= 0 b12=0 Ta < 0 b12=1
bit12=0 [HighByte*16 + LowByte/16]
bit12=1 256-[HighByte*16 + LowByte/16]
39688 ( 9B08 hex )
Displays the heatsink temperature at the end of the last successful start-8
Last temperature -8
16 bit (Highbyte=b11-b8, LowByte=b7-b0)
Ta >= 0 b12=0 Ta < 0 b12=1
bit12=0 [HighByte*16 + LowByte/16]
bit12=1 256-[HighByte*16 + LowByte/16]
39687 ( 9B07 hex )
Displays the heatsink temperature at the end of the last successful start-7
Last temperature -7
16 bit (Highbyte=b11-b8, LowByte=b7-b0)
Ta >= 0 b12=0 Ta < 0 b12=1
bit12=0 [HighByte*16 + LowByte/16]
bit12=1 256-[HighByte*16 + LowByte/16]
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016