SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) No
-
1 ( 1 hex ) Yes
Default
0 ( 0 hex ) No
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
Trip Code Descriptions
Any or all phases missing when the motor is being controlled
104 - 117
Input Side Phase Loss
L1 L2 or L3 phase are missing or at a very low level.
Check all incoming connections.
Check any fuses / breakers incorporated in the power circuit
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Phase L3 missing at the instant of start up
103
Input Side Phase Loss
The L3 phase is either missing or at a very low level
Check all incoming connections.
If a main contactor is being controlled by a digital output set to "Running" check contactor delay is sufficient
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Phase L2 missing at the instant of start up
102
Input Side Phase Loss
The L2 phase is either missing or at a very low level
Check all incoming connections.
If a main contactor is being controlled by a digital output set to "Running" check contactor delay is sufficient
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Phase L1 missing at the instant of start up.
101
Input Side Phase Loss
The L1 phase is either missing or at a very low level
Check all incoming connections.
If a main contactor is being controlled by a digital output set to "Running" check contactor delay is sufficient
The Trip Number shown in PNU Name is a
decimal value
62144 ( F2C0 hex )
Saves all Read /Write parameters to non volatile memory
Save Parameters
Yes : Parameters are permanently written
16 bit unsigned
No : Parameters remain changed until next power cycle
Binary value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 53 of 59