MCSi-78/84
Digital Brushless AC servo drive system - Ref.0707
Parameter incompatibility.
Example.
A drive controls a motor that admits a peak current of 20 A (e.g.: being
the current limit CP20 = 20 A).
If now, a 16A peak motor is connected, the current limit will be beyond
the value allowed for this new motor. It will readjust in RAM memory
certain parameters related to speed and current issuing E502 and
describing the erroneous parameters in the QV22 variable. Resetting
the unit without saving the parameters causes the error to come up
again. The error will go away when executing the GC1 command
because the parameters readjusted to the right values by the drive in
RAM memory are saved in EEPROM memory
Contact Fagor Automation.
Motor not accepted by the drive.
Motor's power voltage is different from that of the drive.
The drive has not detected the sensor.
Check the cabling and the motor connection regarding connector X2.
Then do a reset.
If it doesn't fix it, contact Fagor Automation.
Communication error. After an initial connection, communication errors
keep coming up.
Check the cabling and the motor connection regarding connector X2.
Then do a reset.
If it doesn't fix it, contact Fagor Automation.
E.502
Incompatible parameters
E.506 Motor
table
missing
E.510 Incoherent
combination of motor and feedback
E.801
Encoder not detected
E.802
Defective encoder