V0703-10i / 20i - Installation/Operation - DRO installation - (21/29)
1
The key affects one axis ( = 0) or both ( = 1).
If it affects each axis independently, after pressing this key, one must press
the axis key.
It may toggle from absolute reading mode to incremental. This parameter
determines whether this toggle affects one axis or both (20i).
Factory
setting: "1".
PAR12, PAR13
Travel limit.
To set the negative axis travel limit.
Both parameters admit any value.
This value will be in mm or inches depending on whether the INCH LED is off
or on.
If PAR08 bit 2 = 1, when the axis exceeds the travel distance between both
parameters, the relevant display starts blinking until it is positioned within
these limits.
PAR14
Binary type home search setting.
Digit
8, 7
Not being used at this time (they must be set to "0")
6
If =1, it indicates
mandatory home search on power-up.
5
Direction of the distance-coded Io
( 0 = Increasing , 1 = Decreasing).
4
1 =
Pitch of the distance-coded Io 100 mm, 0 = 20 mm
3
1 =
Pitch of the distance-coded Io: 40 mm. 0 = 20 mm
2
Type of Io of the linear encoder
. (0 = fixed, 1 = distance-coded).
1
If =1,
Linear encoder without I0.
To carry out a home search when the
feedback device does not have a reference mark “Io”, this parameter must be
set to “1”.
Factory setting: "0".