V0703-10i / 20i - Installation/Operation - DRO installation - (19/29)
PAR04
Axis display.
Independent for each axis.
Digit
8, 7, 6, 5, 4
Not being used at this time (they must be set to "0"),
3
Turn the axis display off
. 0 = No, 1 = Yes.
2
Axis display toggle radius/diameter
0 = no toggle, 1 = toggle
1
Axis display
. 0 = radius, 1 = diameters.
Note:
When a rotary axis, the setting of this parameter will be ignored.
PAR05
Shrink or scaling factor
independent for each axis.
Numeric value within ±9.999.
A "0" value means that no factor is to be applied. It is not applied when
reading with respect to machine reference cero (its LED on) or onto the tool
when applying tool compensation (TOOL led on).
The factory setting is “0”.
Note:
When a rotary axis, the setting of this parameter will be ignored.
PAR07
Combine the reading of an axis.
Independent for each axis.
It indicates the number of the axis to be added; “0” means none,
1 = X axis, 2=Y/Z. With the negative sign, the other axis' count will be
subtracted.
Factory setting: "0".
The axis being combined must have the same resolution as the one
combined with (PAR01, PAR02, PAR03).
Possible values:
-2 to 2. (20i)
Note:
When a rotary axis, the setting of this parameter will be ignored.
PAR08
Use of alarms
.
Indicates whether the alarms for feedrate, travel limits and feedback will be
activated or not.
Digit
8, 7, 6, 5
Not being used at this time (they must be set to “0”)
4
Active value of the feedback alarm.
(0=low, 1=high)
3
Detect feedback alarm provided by the linear encoder.
0 = No, 1 = Yes.
2
Detect travel limits (PAR12 and PAR13).
When this alarm is activated, the
axis value blinks.
The blinking axis error is cleared by returning the axis within its limits