Construct the chimney breast against the build-in frame  (see fig. 1.1 B).  

Keep a minimum margin of 3mm between chimney breast and the appliance in 

connection with the expansion of the appliance. 

 

The depth of the recess into the chimney breast has no influence on the removal of 

the glass. 

 

5

 

Removing the glass 

 

Remove the cover strips on the left and right hand side (see fig. 2.1). 

 

Remove the glass clips, by using a screwdriver (see fig. 2.2). 

 

Place the suction discs onto the glass (see fig. 1.6). 

 

Slide the glass upwards so that the bottom edge is released. Now gradually 

move the bottom edge of the glass forwards and lower the glass (see fig. 2.3). 

 

To replace the glass repeat the process in reverse order. 

Remove all fingerprints from the glass, these will be burned into it once the appliance is 

used. 

 

6

 

Placing the decorative material 

It is not allowed to add different or more materials to the combustion chamber. 

Always keep the pilot burner free from decorative material! 

Do not toss all the decorative material onto the burner all at once, as the very fine dust 

may block the holes in the burner. 

6.1

 

Imitation logs 

 

Spread the vermiculate preferably by hand over the tube burners. The surface of 

the pebbles may be very slightly elevated from the burner plate but it should be 

level throughout the entire length. 

 

Place the imitation logs according to instructions. (see fig. 3.1 or the instruction 

card). 

 

It is optional whether you apply chips to the combustion chamber or not. Prevent 

chips from covering the burner, this has a negative effect on the fire image. 

 

Start the pilot en main burner, according to the instructions in the user’s manual. 

Assess whether the flame distribution is correct. 

 

Place the glass and check the flame picture into the appliance. 

Содержание Fyn 450 ENG

Страница 1: ...Installation manual Fyn 450 ENG 40010929 1840...

Страница 2: ...1 L 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3...

Страница 3: ...2 L 3 1 3 2 4 0 4 1 4 2 4 3 4 4...

Страница 4: ...ome hotter than 100 C Do not use the remote control and or app outside the room where the fire is located So that you are always aware of the situation around the fireplace when it is being operated C...

Страница 5: ...p a free distance of min 50mm on the back site of the fire See fig 1 1 For the finish use special stucco min 100 C resistant or glass fibre wallpaper to prevent discoloration or cracks etc Recommended...

Страница 6: ...100mm should have a CE mark for temperatures up to 600 Celsius The chimney should comply with the following requirements The diameter of the flue system must be at least 150x150mm There should be no m...

Страница 7: ...rizontal parts must be installed at a 3 degree slope up away the appliance Build up the system from the appliance If this is not possible you should make use of an adjustable pipe For fitting the syst...

Страница 8: ...e appliance is used 6 Placing the decorative material It is not allowed to add different or more materials to the combustion chamber Always keep the pilot burner free from decorative material Do not t...

Страница 9: ...and easily 7 2 Checking for gas leakage Check all connections and joins for possible gas leaks by means of a gas leak detector or spray 7 3 Checking the burner pressure and the pre pressure Check whe...

Страница 10: ...leakage in case of blue flames Whether the correct flue restrictor has been mounted The outlet o Wall terminal is installed correctly o Roof terminal is fitted and sited correctly The flue system is c...

Страница 11: ...ed with a dry cloth Clean the glass with Faber glass polish Note prevent fingerprints on the glass these will be burned into it once the appliance is used and cannot be removed anymore Carry out the c...

Страница 12: ...HL Start length STL This is the first part that is placed on the fire and represents a certain value fig 12 1 12 2 and 12 3 A N and F This value is in the top row of the table see restrictor table 11...

Страница 13: ...gle of 30 or 45 fig 12 1 C Fill in only in combination with at least 2x 30 or 45 bends in the vertical part Restrictor table See the restrictor table at the right vertical TVH and horizontal length TH...

Страница 14: ...0 40 x x x x 10 65 1 65 65 60 60 50 40 x x x x 11 65 1 65 65 60 60 50 40 x x x x 12 65 1 65 65 60 60 50 40 x x x x 13 65 1 65 65 60 60 50 40 x x x x 14 65 1 65 65 60 60 50 40 x x x x 15 65 1 65 65 60...

Страница 15: ...14 L 12 Examples flue materials Fig 12 1 Fig 12 2 Fig 12 3...

Страница 16: ...Bend in horizontal direction x 1 flue pipes at an angle in meters x 0 7 meter Calculation Total rounded value Total Vertical Height TVH measured height meter Total Horizontal Length THL Value Starter...

Страница 17: ...er to 130 200 and 1 meter 130 200 after that reduce to 100 150 and everything 100 150 0 5 Restrictor size Value for the comma Extra information Value behind the comma Search in the table at TVH and TH...

Страница 18: ...er requirement for permanent pilot light if applicable Ppilot 0 11 0 11 0 11 kW Additional electricity consumption At nominal heat output elmax 0 0 0 kW At minimum heat output elmin 0 0 0 kW In standb...

Страница 19: ...ance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable out...

Страница 20: ...19 L 16Troubleshooting guide...

Страница 21: ...20 L...

Страница 22: ...21 L...

Страница 23: ...22 L 17Dimensional drawings 17 1 Fyn 450...

Страница 24: ...23 L 17 2 Ventilation grid...

Страница 25: ...24 L 17 3 Remote access door...

Страница 26: ...25 L...

Страница 27: ...26 L...

Страница 28: ......

Отзывы: