16 <
<
<
<
L
found value
………………………………
………………….. mm
mark
Install the air restrictor plate, see installation manual
0,1
Install adapter 100/150 direct on top of the fire
0,2
In case of wall terminal, install adapter 100/150 before the
last bend, incase of roof terminal just before the terminal.
0,3
In case of roof terminal (always size 100/150) install the
100/150 adapter just before the terminal.
Wall terminal 130/200
0,4
From the fire first an adjuster to 130/200 and 1 meter
130/200, after that reduce to 100/150 and everything
100/150.
0,5
Restrictor size = Value for the comma
Extra information = Value behind the comma
Search in the table at TVH and THL and enter the value that is found.
If the detected value is a number, check whether the completed STL is higher or equal to the value in
the table.
Is the STL value lower as specified in the table then the installation is not possible.
Solution: Start length to low, see for the minimum length in the top row of the table.
Is the found value X, then the installation is not possible.
Solution: Change the TVH or THL.
Results
Содержание Fyn 450 ENG
Страница 1: ...Installation manual Fyn 450 ENG 40010929 1840...
Страница 2: ...1 L 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3...
Страница 3: ...2 L 3 1 3 2 4 0 4 1 4 2 4 3 4 4...
Страница 15: ...14 L 12 Examples flue materials Fig 12 1 Fig 12 2 Fig 12 3...
Страница 20: ...19 L 16Troubleshooting guide...
Страница 21: ...20 L...
Страница 22: ...21 L...
Страница 23: ...22 L 17Dimensional drawings 17 1 Fyn 450...
Страница 24: ...23 L 17 2 Ventilation grid...
Страница 25: ...24 L 17 3 Remote access door...
Страница 26: ...25 L...
Страница 27: ...26 L...
Страница 28: ......