The pressure must agree with the value indicated on the registration plate. In case 

of deviations, get in touch with the manufacturer. 

 

Close the pressure gauge nipples and check these for gas leaks.  

7.4

 

Checking the flame picture 

Allow the appliance to burn for at least 20 minutes at full and then check the flame 

picture for: 

 

Distribution of the flames. 

 

Color of the flames. 

 

If either one or both points are unacceptable, then check: 

 

The positioning of the imitation logs and/or the quantity of pebbles or chips on the 

burner. 

 

The connections of the flue materials for leakage (in case of blue flames). 

 

Whether the correct flue restrictor has been mounted. 

 

The outlet:  

o

 

Wall terminal is installed correctly. 

o

 

Roof terminal is fitted and sited correctly. 

 

The flue system is correctly calculated.  

 

8

 

Instructing the client 

 

Recommend that the appliance be serviced annually by a competent person in 

order to guarantee a safe use and a long lifespan. 

 

Advise and instruct the client about maintenance and cleaning of the glass. 

Emphasize the risk of burning in fingerprints. 

 

Instruct the client about the operation of the appliance and the remote control 

unit, including the replacement of the batteries and adjusting the receiver for 

initial use. 

 

Hand over to the client: 

o

 

Installation manual  

o

 

User manual 

o

 

Logset instruction card  

o

 

Suction lifters   

 

 

 

Содержание Fyn 450 ENG

Страница 1: ...Installation manual Fyn 450 ENG 40010929 1840...

Страница 2: ...1 L 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3...

Страница 3: ...2 L 3 1 3 2 4 0 4 1 4 2 4 3 4 4...

Страница 4: ...ome hotter than 100 C Do not use the remote control and or app outside the room where the fire is located So that you are always aware of the situation around the fireplace when it is being operated C...

Страница 5: ...p a free distance of min 50mm on the back site of the fire See fig 1 1 For the finish use special stucco min 100 C resistant or glass fibre wallpaper to prevent discoloration or cracks etc Recommended...

Страница 6: ...100mm should have a CE mark for temperatures up to 600 Celsius The chimney should comply with the following requirements The diameter of the flue system must be at least 150x150mm There should be no m...

Страница 7: ...rizontal parts must be installed at a 3 degree slope up away the appliance Build up the system from the appliance If this is not possible you should make use of an adjustable pipe For fitting the syst...

Страница 8: ...e appliance is used 6 Placing the decorative material It is not allowed to add different or more materials to the combustion chamber Always keep the pilot burner free from decorative material Do not t...

Страница 9: ...and easily 7 2 Checking for gas leakage Check all connections and joins for possible gas leaks by means of a gas leak detector or spray 7 3 Checking the burner pressure and the pre pressure Check whe...

Страница 10: ...leakage in case of blue flames Whether the correct flue restrictor has been mounted The outlet o Wall terminal is installed correctly o Roof terminal is fitted and sited correctly The flue system is c...

Страница 11: ...ed with a dry cloth Clean the glass with Faber glass polish Note prevent fingerprints on the glass these will be burned into it once the appliance is used and cannot be removed anymore Carry out the c...

Страница 12: ...HL Start length STL This is the first part that is placed on the fire and represents a certain value fig 12 1 12 2 and 12 3 A N and F This value is in the top row of the table see restrictor table 11...

Страница 13: ...gle of 30 or 45 fig 12 1 C Fill in only in combination with at least 2x 30 or 45 bends in the vertical part Restrictor table See the restrictor table at the right vertical TVH and horizontal length TH...

Страница 14: ...0 40 x x x x 10 65 1 65 65 60 60 50 40 x x x x 11 65 1 65 65 60 60 50 40 x x x x 12 65 1 65 65 60 60 50 40 x x x x 13 65 1 65 65 60 60 50 40 x x x x 14 65 1 65 65 60 60 50 40 x x x x 15 65 1 65 65 60...

Страница 15: ...14 L 12 Examples flue materials Fig 12 1 Fig 12 2 Fig 12 3...

Страница 16: ...Bend in horizontal direction x 1 flue pipes at an angle in meters x 0 7 meter Calculation Total rounded value Total Vertical Height TVH measured height meter Total Horizontal Length THL Value Starter...

Страница 17: ...er to 130 200 and 1 meter 130 200 after that reduce to 100 150 and everything 100 150 0 5 Restrictor size Value for the comma Extra information Value behind the comma Search in the table at TVH and TH...

Страница 18: ...er requirement for permanent pilot light if applicable Ppilot 0 11 0 11 0 11 kW Additional electricity consumption At nominal heat output elmax 0 0 0 kW At minimum heat output elmin 0 0 0 kW In standb...

Страница 19: ...ance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable out...

Страница 20: ...19 L 16Troubleshooting guide...

Страница 21: ...20 L...

Страница 22: ...21 L...

Страница 23: ...22 L 17Dimensional drawings 17 1 Fyn 450...

Страница 24: ...23 L 17 2 Ventilation grid...

Страница 25: ...24 L 17 3 Remote access door...

Страница 26: ...25 L...

Страница 27: ...26 L...

Страница 28: ......

Отзывы: