manualshive.com logo in svg
background image

INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105

30

Revision 3

•  Programmable inputs, P channels

There are six programmable inputs available in the EP105.

The instructions are identical for all six programmable inputs, apart from the channel number – input 1 has channel number 

P1nn, input 2 has channel number P2nn, etc. The settings below are for input 1.

Activate input 1 by setting P100 to 1. Note that the indication for the programmable input works even if  the input is disabled.

The following channels are used to set the function for the programmable input.
P160, Control function

Option 0 disables the control function on the programmable input, 1 is for the opening function, 2 is for the closing 

function, and 3 is for the stop function. Option 4 means open the gate if  it is not already open, then close it as soon as it 

is in the open position. Option 5 means open, stop and close alternately. Five seconds after the last command, the next 

command is automatically set to open again. 

P161, Type of  control signal.

Use this channel to specify whether you want the signal to be a constant signal throughout the signal duration or just for the 

on flank (the automatic control unit interprets the signal as a pulse). If  the pulse option is set, hold-to-run does not work 

if  the safety edge is defective but the door can be operated via another input even if  the input is activated.

P162, Half  operation

To only open motor 1 set the value to 1, to only open motor 2 set the value to 2, and to open both motors 1 and 2 set the 

value to 3.

P163, Limited opening

With set value 0, the door opens to its end position, at set value 1 the door opens with encoder the number of  degree 

specified in L116 and/or L117 or with limit switch, during the set time in L216 and/or L226.

 

P170, Motor lock.

When the value is set to 1 the door will start opening or closing when there is a signal on the input and another input is 

controlled. This is to ensure that the motor lock is unlocked before opening or closing takes place. 

P175, Delayed opening

The motors will not start the opening until the input has been activated for a set time. This may be used, for example, to 

prevent unintended opening signals.

P180, Park

Use this channel to park the door. Option 0 disables the function, option 1 parks the door in the open position and waits 

for a new control signal before the door is closed. To use a timer for parking and opening the door, set P160 to 1 and P180 

to 2. The input will then send a command to open the door in response to a signal, and keep the door open for as long as 

there is a constant signal at the input.

P190, Interlock opening

Use this parameter with the value 1 if  you want the input to open a local door and also forward the open signal to a remote 

door.

P196, Blocking disabled for local and remote doors

Set the value to 1 to disable blocking for the local and remote doors.

P198, Automatic closing disabled for local and remote doors

Set the value to 1 to disable automatic closing for local and remote doors.

•  Automatic closing 

To prevent the door being left open, you can configure the unit to close it automatically after a specified period. Any time from 

0.1 to 600.0 seconds can be chosen. The timer starts when the door has stopped moving. If  any control input or safety device 

is activated in the closing direction, the timer is stopped and the time starts counting from the set value again.

If  you use automatic closing, it is a good idea to connect a wireless transmitter or a pull cord to an unused input. This is to 

allow passing users to send a new opening signal and reset the automatic closing time. 

You can use programmable inputs and a timer to disable automatic closing at particular times of  the day. 

The time remaining until automatic closing takes place can be read off  in channel C019.

Configuring automatic closing

Choose channel C500 and set a suitable time between 0.1 and 600.0 seconds before automatic closing takes place. Note 

that only times with whole seconds can be indicated between 10.0 and 600.0. 0.0 means that automatic closing is disabled.

Stop function

The automatic control unit has an adjustable stop function. The function applies to the normal stop buttons and also 

the stop function in programmable inputs. The initial setting is that when the stop button is pressed the countdown for 

automatic closing does not restart.

Содержание DAAB EP105

Страница 1: ...INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105...

Страница 2: ...11 Installing the PCB 11 Connecting a safety edge 12 Connecting safety edges and photocells 12 Connecting an encoder electronic limit switch 13 Connecting a mechanical limit switch microswitch 13 Con...

Страница 3: ...ulse mode and hold to run mode 29 Checking safety functions 29 Setting electric motor braking 29 Programmable inputs P channels 30 Automatic closing 30 Run on time with mechanical limit switches 31 Ru...

Страница 4: ...s SS EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environments This declaration relates to automatic cont...

Страница 5: ...or the controlled units Cleaning and maintenance must not be performed by children The EP105 control unit or the accessories recommended by FAAC Nordic AB must not be modified without the express cons...

Страница 6: ...ervice and maintenance Regular inspection is required of the external safety features of the EP105 such as safety edges stop buttons photocells load guards and safety loops The condition of the enclos...

Страница 7: ...oved for use with the particular cable Cables outside the enclosure must be securely fixed to the surrounding structure They must not hang loose and there must be no possibility of them catching on pa...

Страница 8: ...tor If a symmetrical single phase motor is used as shown on the left make the following changes EP105 1 Swap the cable at X12 L1 1 with X12 L1 C1 EP105 2 Remove the cable between X11 L2 1 and X4 L2 2...

Страница 9: ...ocumentation Instruction manual for drive unit Instruction manual for the door gate or barrier Disposal of electronic equipment The EP105 is an electronic product and as such is classified as hazardou...

Страница 10: ...edge while opening Variable impedance range 1 0 9 9 k power capability at least 0 5 W Safety circuit Maximum resistance 3 total in the whole safety circuit Cable length at 0 75 mm2 max 60 m Cable leng...

Страница 11: ...sk Enclosure The PCB must be installed in an enclosure designed for the surrounding environment and must protect the electronics from moisture dust and contact The enclosure must provide protection to...

Страница 12: ...he maximum number of safety edges connected in series with an impedance of 8 2 k is six per input Note that the impedance used for a safety edge must be checked and entered into the EP105 on commissio...

Страница 13: ...DB405 Motor 2 Right position Control unit 14 17 1 2 3 1 2 3 34 L O1 L O2 GND 24V 24V GND GND L OUT L OUT 24V 13 24V 16 Motor 1 Left position Motor 2 Right position Connecting a mechanical limit switch...

Страница 14: ...switches to economy mode with reduced brightness Press any button to return to normal mode Display Description Cnnn Channel number for the EP105 dnnn Channel number for the vehicle detector Fnnn Chan...

Страница 15: ...n with the factory setting are displayed With C999 2 channels for power supply motor protection and limit switches are displayed This display mode is used to set open and closed position With C999 3 c...

Страница 16: ...A Connection point Signal encoder or limit switch open motor 1 Safety edge 1 closing movement SE C1 Safety edge 2 closing movement SE C2 Safety edge 1 opening movement SE O1 Safety edge 2 opening move...

Страница 17: ...is not programmed quick flashing means hold to run without limit switch L O2 Motor 2 not finished opening extinguished in closed position flashing means the input is not programmed quick flashing mean...

Страница 18: ...ng movement and those fitted to the back provide protection for the opening movement Safety edges providing protection for the closing movement are connected to SE C1 and SE C2 while SE O1 and SE O2 a...

Страница 19: ...on L112 Open position L 1 1 1 P o s i t i o n r e a d o u t Motor protection Read the motor current during operation in C251 and enter this value in C252 for opening and in C253 for closing E201 means...

Страница 20: ...tion personal protection is not normally required and C240 is set to 0 00 Set C033 to 3 pulse to activate the load guard After the load guard has tripped the indication M2 flashes and the message n073...

Страница 21: ...mechanically secured and installed according to the applicable instruction manuals All components are correctly connected and installed by authorised installers before switching on the power supply T...

Страница 22: ...re 1 is left and 2 is right Keep the factory setting for L002 at 0 Run the motor hold to run to the closed position then read channel L111 for motor 1 and specify the value as closed position in chann...

Страница 23: ...ternal connectors When a frequency inverter is used the instructions in the user manual for the DB409 must be followed The illustrations show motor protection settings for motor 1 With value set too h...

Страница 24: ...rotection Before changing the other settings you will need the following information about the unit to be tested Check supply voltage to which the unit will be connected Check the required current the...

Страница 25: ...ts If the fixed limits result in excessive crushing force you can adjust the crushing force by reducing the limit settings in C232 C242 for the opening movement and C233 C243 for the closing movement...

Страница 26: ...impedance in C115 C125 and C135 for the safety edge concerned To completely disable safety edge inputs that are not used set C111 C121 C131 and or C141 to 0 for the safety edge concerned C111 setting...

Страница 27: ...ified in channel C493 Option 2 Stop stops the door without reversing Must be used with care as the lack of the reverse function means someone may become trapped Reverse delay The delay between activat...

Страница 28: ...6 configured for photocell There is also an option for an extra input for photocell or vehicle loop by using terminal 27 and changing P600 to 2 Set the desired safety function in P640 P641 P642 and P...

Страница 29: ...the automatic control unit automatically switches to hold to run mode in the direction in which there is a fault Even when the safety edge or photocell vehicle loop are activated you can still open a...

Страница 30: ...has been activated for a set time This may be used for example to prevent unintended opening signals P180 Park Use this channel to park the door Option 0 disables the function option 1 parks the door...

Страница 31: ...d for vehicle loops you can configure the internal close signal depending on the preferred direction sensing mode in LOOP1 and LOOP2 and the PHOTO input See the channel reference for all possible valu...

Страница 32: ...configured in C436 it is possible for example to set the door to close tightly against rubber strips without triggering the load guard or safety edge The disengagement angles are to be reduced to as...

Страница 33: ...with a grey background are readout channels so they cannot be changed The S symbol means that the channel is a safety setting and any change in value must be documented in the log book with a name an...

Страница 34: ...pulse and close with hold to run and load guard active 2 Open with hold to run and close with pulse and load guard active 3 Open and close with pulse and load guard active 4 Open and close with hold...

Страница 35: ...C1 and SE O1 must be connected to motor 1 SE C2 and SE O2 must be connected to motor 2 The safety edge function is attached to the motor concerned 3 SE C1 or SE C2 can be connected to either motor 1...

Страница 36: ...135 2 Fixed limits between 5 k and 15 k S C132 Reverse stop with activated safety edge SEO1 1 2 1 26 1 Reverse 2 Stop S C133 Control of external protection connected to SE O1 0 1 1 24 0 No check 1 Tes...

Страница 37: ...AC Set motor power readout for personal protection motor 1 0 00 and 0 12 0 35 kW 0 20 25 C231A Motor power readout motor 1 0 00 1 99 kW S C232A Set load guard limit for motor 1 opening 0 05 1 99 kW 0...

Страница 38: ...engagement angle 1 Activated according to C340 C342 Safety function in opening movement 0 4 0 28 0 Disabled 1 Reverse to fully closed 2 Stop with automatic restart of automatic closing 3 Stop wait for...

Страница 39: ...run on time or disengagement angle with load guard triggered L117 L127 L213 L223 0 1 1 31 0 No reversing 1 Reversing in closing movement C460 Time delay before second motor starts Start of motor 2 is...

Страница 40: ...detection PHOTO and LOOP2 must first be activated simultaneously then close when either PHOTO or LOOP2 is clear 07 Presence detection PHOTO LOOP1 and LOOP2 must first be activated simultaneously close...

Страница 41: ...til remote door is open 3 Blocking of close on local door until remote door is closed C615 In block of local door 0 3 3 0 Stopped local door does not disable blocking of remote door Local door does no...

Страница 42: ...talled C705 Encoder card DB405 0 1 0 0 Not installed does not affect display of L channels 1 Installed the settings in L001 and L002 also control display of L channels C707 Output card DB407 0 1 0 0 N...

Страница 43: ...o step up or down _____ End of the list followed by the oldest message when the plus button is pressed C904 Message on display and in error code list 0 1 1 0 Message is neither displayed nor stored in...

Страница 44: ...mited opening motor 1 0 200 degrees 45 L117 1 Angle for disconnection of safety edge load guard and photocell from the end of the closing movement motor 1 in combination with C436 C341 and C448 0 30 d...

Страница 45: ...05 0 L221 A Running time readout motor 2 000 999 seconds L222 AC Run on time following limit switch open motor 2 0 00 7 99 seconds 0 00 22 L223 A Run on time following limit switch closed motor 2 0 00...

Страница 46: ...ier cannot be operated without a signal at programmable input 1 If the signal disappears ongoing movement stops P175 Opening via input after activation during set time input will not open the gate unt...

Страница 47: ...erated without a signal at programmable input 2 If the signal disappears ongoing movement stops P275 Opening via input after activation during set time input will not open the gate until it has been a...

Страница 48: ...erated without a signal at programmable input 3 If the signal disappears ongoing movement stops P375 Opening via input after activation during set time input will not open the gate until it has been a...

Страница 49: ...a signal at programmable input 4 If the signal disappears ongoing movement stops P475 Opening via input after activation during set time input will not open the gate until it has been activated for th...

Страница 50: ...0 1 0 30 0 Disabled 1 The barrier cannot be operated without a signal at programmable input 5 If the signal disappears ongoing movement stops P575 Opening via input after activation during set time in...

Страница 51: ...angle 1 Activated according to P640 P642 Protection in opening movement 0 4 1 28 0 Disabled 1 Reverse to fully closed 2 Stop with automatic restart of automatic closing 3 Stop wait for new control si...

Страница 52: ...0 30 0 Disabled 1 Automatic closing disabled after the input is activated reset by another control signal 2 Automatic closing disabled by a constant signal P690 Interlock opening 0 1 0 30 0 Disabled...

Страница 53: ...tivated value in C240 Check C211 it must not be longer than 0 06 seconds C212 cannot be longer than 2 seconds C493 cannot be longer than 0 20 seconds E028 Brake selected when C202 is set to 2 4 or 5 C...

Страница 54: ...motor 1 Check the connection and the settings as described in Instruction Manual for DB409 Address must be set for the frequency converter E652 No response from frequency inverter motor 2 Check the c...

Страница 55: ...fety edge is not functional set channel C113 to 0 E962 SE C2 did not change to low during the external test Check that the safety edge is functional if the safety edge is not functional set channel C1...

Страница 56: ...door reverses and the red LEDs M1 M2 start flashing Is the load guard correctly installed Has the correct supply voltage been set Mechanical fault Does the door move easily when decoupled Are the red...

Страница 57: ...licably close by itself without an error message or alarm LEDs Try to operate the door again opening and closing Also check C020 for the most recent stop cause Cross check the number with the channel...

Страница 58: ...INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105 58 Revision 3 Notes...

Страница 59: ...INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105 59 Revision 3 Notes...

Страница 60: ...Revision 3 FAAC Nordic AB Box 125 SE 284 22 Perstorp 46 435 77 95 00 www faac se support faac se...

Отзывы: