12. DIAGNOSTICS
12.1 LEDS CHECK
LED
STATUS IDLE
DL1
Board power
on
off
DL2
Microprocessor Power
on
off
DL3
BUS 2easy “BUS MON“
diagnostics.
See BUS 2easy device
registration
DL4
RADIO1
active
not active
DL5
RADIO2
active
not active
DL6
Error/alarm “ERROR”
active
not active
DL7
BUS 2easy device ACTIVE
active
not active
DL8
USB
active
not active
DL10
OPEN A
active
not active
DL11
OPEN B
active
not active
DL12
CLOSE
active
not active
DL13
STOP
DL14
SAFE OP
not active
active
DL15
SAFE CL
not active
active
DL16
Accessories power
on
off
12.2 AUTOMATION SYSTEM STATUS
CHECK
If you are not in programming mode, the display of
the E4000I, indicates the automated system status:
00
CLOSED
01
OPEN
02
Stationary then OPENS
03
Stationary then CLOSES
04
PAUSED
05
Opening
06
Closing
07
BUS 2easy device verification in progress
08
FAIL SAFE in progress
09
Pre-flashing and then OPENS
10
Pre-flashing and then CLOSES
13
Sleep
12.3 ENCODER OPERATION CHECK
1. Select parameter
M1
in Basic programming. The
display shows
--.
2. Keep the
+
button pressed. The display indi-
cates
oP
and the gate opens. The flashing point
between the two letters indicates that the encoder
is operating correctly.
3. Keep
the
-
button pressed. The display indicates
cL
and the gate closes. The flashing point be-
tween the two letters indicates that the encoder
is operating correctly.
12.4 ALARMS
The alarms provide information regarding the condi-
tion or current phase of the automation system and
any malfunctions that do not prevent it from oper-
ating. Alarms are indicated by the ERROR LED (
DL6
)
flashing on the board. To check for any active alarms,
press the + and - buttons simultaneously while the
display is indicating the automated system status.
Al
appears on the display followed by a numerical code:
Alarms
Intervention required
20
Obstacle during opening Remove obstacle.
21
Obstacle during closing Remove obstacle.
24
LAMP output short-cir-
cuited
Remove the cause of the short
circuit.
27
Number of consecutive
obstacles during open-
ing exceeded.
Remove obstacle.
28
Number of consecutive
obstacles during closing
exceeded.
Remove obstacle.
30
XF radio code memory
full
Delete any unused radio codes or
use an additional radio module.
40
Request assistance
Contact the installer to carry out
maintenance.
45
Battery operation
Board powered with emergency
battery
56
Fail Safe in progress
Wait until the test ends and if
necessary, check the operation of
the safety devices.