Operating Manual
7
Warning!
For GROUP I applications ONLY, the changing of the cells in the
hazardous area or the transportation of spare cells into the hazardous
area is NOT PERMITTED.
Warning!
For GROUP II applications ONLY, the user shall not carry more than a
maximum of 2 spare Duracell Plus MN1500 or Duracell Procell MN1500
cells into the hazardous area. Precautions shall be taken to prevent
short circuiting of un-protected cell terminals. Discharged cells shall be
removed from the hazardous area.
Warning!
For Class 1 Division 1 applications ONLY, the user shall not carry more
than a maximum of 2 spare Duracell Plus MN1500, Duracell Procell
MN1500/PC1500 or Energizer E91 cells into the hazardous area.
Precautions shall be taken to prevent short circuiting of un-protected
cell terminals. Discharged cells shall be removed from the hazardous
area.
Warning!
For GROUP II applications ONLY the rated ambient temperature range of
the equipment is from -20
o
C to 60
o
C.
Warning!
For GROUP I applications ONLY the rated ambient temperature range of
the equipment is from 0
o
C to 60
o
C.
Warning!
For Class 1 Division 1 applications ONLY the rated ambient temperature
range of the equipment is from -20
o
C to 55
o
C/50
o
C dependent on the
cells used (see Table 1).
Warning!
If any damage to the iCAM501U is found which may invalidate the
required safety minimum IP rating (IP54 for group I applications), (IP20
for group II and class 1 division 1 applications), the iCAM501U shall be
removed from the hazardous area.
Important
Any repairs or replacement of parts MUST be performed by the
manufacturer or its nominated sub-contractor or agent.
Important
The iCAM501U contains no user serviceable parts. The main part of the
enclosure must not be opened under any circumstances.
Table 1Cells approved for use with iCAM501U units
Application:
Duracell Plus
MN1500
Duracell Procell
MN1500
Duracell Procell
PC1500
Energizer E91
iCAM501U
ATEX GROUP II
OK, T4 at 60
o
C
OK, T4 at 60
o
C
CANNOT BE
USED
CANNOT BE
USED
iCAM501U
ATEX GROUP I
OK, T4 at 60
o
C
OK, T4 at 60
o
C
CANNOT BE
USED
CANNOT BE
USED
iCAM501U
CLASS
1DIVISION 1
OK, T4 at 55
o
C
OK, T4 at 55
o
C
OK, T3C at 50
o
C
OK, T3C at
50
o
C
Содержание iCAM50
Страница 4: ...Operating Manual 4...
Страница 36: ...Operating Manual 36 6 Certification 6 1 iCAM501U EC Declaration of Conformity...
Страница 37: ...Operating Manual 37 6 2 iCAM502 EC Declaration of Conformity...
Страница 38: ...Operating Manual 38 6 3 iCAM501U Class 1 Division 1 Certificate of Compliance...
Страница 39: ...Operating Manual 39...
Страница 40: ...Operating Manual 40...
Страница 41: ...Operating Manual 41...