8. THIRD PROGRAMMING LEVEL PARAMETERS 

Press and hold the SCROLL and RETURN keys simultaneously for 5 seconds to enter 
this level from the previous programming level. To return to normal operation at any 
time, press the RETURN key. 

rEmo:

 Remote/Local toggle parameter. Set to "0" for local mode or "1" for optional 

RS-485 PC communications remote mode. In remote mode, the controller's 
keypad is inactive and only a connected PC can change the controller's 
parameters.  In local mode the controller's keypad is active.

 

P-L:

 Parameter Lock. This security feature locks out selected programming levels 

prohibiting tampering and inadvertent programming changes. Depending upon 
its setting, only certain parameters will display, refer to the list below. 
Allowable setting range: 0 to 15; 

 
0 - All parameters displayed are adjustable (level 1 parameters: A1SP, A2SP) 
1 - Same as ‘0’(level 1 parameters displayed: Ramp, A1SP, A2SP) 
2 - Same as ‘0’(level 1 parameters displayed: oPoF, A1SP, A2SP) 
3 - Same as ‘0’(level 1 parameters displayed: Ramp, oPoF, A1SP, A2SP) 
 

4 - same as '0', w/level 4 locked 

10 - same as '2', but levels 3, 4 locked 

5 - same as '1', w/level 4 locked 

11 - same as '3', but levels 3, 4 locked 

6 - same as '2', w/level 4 locked 

12 - same as '0', but levels 2, 3, 4 locked 

7 - same as '3', w/level 4 locked 

13 - same as '1', but levels 2, 3, 4 locked 

8 - same as '0', w/levels 3, 4 locked 

14 - same as '2', but levels 2, 3, 4 locked 

9 - same as '1', w/levels 3, 4 locked 

15 - same as '3', but levels 2, 3, 4 locked 

 

A1Fu: 

Alarm 1 Function. Select an Alarm / Timer function from the function list in 

Appendix A. 

A2Fu: 

Alarm 2 Function. Select an Alarm function from the alarm functions list in 

Appendix A. 

A1HY:

 Hysteresis for Alarm 1. The Setting range is 0.0 to 25.5% of the controller's span 

settings. The controller's Span extends from the value programmed in 'LoLt' to 
the value programmed in the 'HiLt' parameter (Low and High Limits).  Hysteresis 
is used to eliminate relay "chatter" by creating a deadband that extends from the 
alarm setpoint down or up (depending upon the alarm type) where no relay 
action can occur. The larger the hysteresis value the less the possibility of relay 
chatter. 

A2HY:

 Same as A1HY except for Alarm 2. 

Act: 

Primary Output (Output 1) control action.  Set to "0" for cooling (direct) action or "1" 

for heating (reverse) action. Secondary Output (Output 2) is automatically 
configured as a cooling output. 

unit: 

Unit of measure selection.  Program as follows: 

Set to '0' for degrees F  
Set to '1' for degrees C 
Set to '2' for analog inputs 

dP

: Decimal Point selection.

 

Set to '00' for no decimal point 
Set to '01' for 0.1 resolution 
Set to '02' for 0.01 resolution (cannot use this setting for temperature inputs) 
Set to '03' for 0.001 resolution (cannot use this setting for temperature inputs) 

Ct:

 Primary Control Output 1 Cycle Time. Range: 0 to 100 seconds. This is the rate at 

which the controller makes automatic output adjustments. The longer the time, 

Содержание 96VTR

Страница 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Страница 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Страница 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Страница 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Страница 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Страница 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Страница 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Страница 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Страница 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Страница 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Страница 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Страница 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Страница 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Страница 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Страница 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Отзывы: