setpoint changes always remaining a programmed number of units from the main 
setpoint. 

'02'  Process High Alarm: 

Relay trips when the process (PV) exceeds the value 

programmed at "A1SP" or "A2SP". Process alarms are fixed, absolute values and 
do not change as the main control setpoint changes. 

'03'  Process Low Alarm: 

Relay trips when the process (PV) falls below  the value 

programmed at "A1SP" or "A2SP". Process alarms are fixed, absolute values and 
do not change as the main control setpoint changes. 

'04'  Deviation High Alarm with Standby Sequence: 

Same as the Deviation High 

Alarm but no relay action takes place until the process PV reaches the setpoint for 
a second time.   Standby sequence is also known as "Startup Inhibit" and is useful 
for avoiding alarm trips during startup. 

'05'  Deviation Low Alarm with Standby Sequence: 

Same as the Deviation Low 

Alarm but no relay action takes place until the process PV reaches the setpoint for 
a second time.   Standby sequence is also known as "Startup Inhibit" and is useful 
for avoiding alarm trips during startup. 

'06'  Process High Alarm with Standby Sequence: 

Same as the Process High Alarm 

but no relay action takes place until the process PV reaches the setpoint for a 
second time.   Standby sequence is also known as "Startup Inhibit" and is useful 
for avoiding alarm trips during startup. 

'07'  Process Low Alarm with Standby Sequence: 

Same as the Process Low Alarm 

but no relay action takes place until the process PV reaches the setpoint for a 
second time.   Standby sequence is also known as "Startup Inhibit" and is useful 
for avoiding alarm trips during startup.

 

The following Alarm Timer Selections are available for Alarm 1 only 

'08'  EVENT ON-Timer:  

Upon power-up the alarm is de-energized.  When the PV = SV 

the alarm relay remains de-energized. When the timer counts down to zero, then 
the relay energizes. Set the timer at parameter 'time' in Programming Level 1. 
See Table IV below. 

'09'  EVENT OFF-Timer

:   Upon power-up the alarm relay energizes.  When the PV = 

SV the alarm relay remains energized. When the timer counts down to zero, then 
the relay de-energizes. Set the timer at parameter 'time' in Programming Level 1. 
See Table IV below. 

'10' SOAK ON-Timer:  

Upon power-up the alarm relay is de-energized.  When the PV = 

SV the alarm relay energizes. When the timer counts down to zero the relay de-
energizes. Set the timer at parameter 'time' in Programming Level 1. See Table IV 
below. 

'11' SOAK OFF-Timer: 

Upon power-up the alarm relay energizes.  When the PV = SV 

the alarm relay de-energizes. When the timer counts down to zero the relay 
energizes. Set the timer at parameter 'time' in Programming Level 1. See Table IV 
below . 

Table IV - EVENT and SOAK Timer Relay States 

A1Fu

 

Setting

 

 

ALARM RELAY MODE

 

Controller

 

at Power-up

 

When PV=SV

Timer Starts

 

After Timer

 

Counts Down

8

 EVENT 

ON-TIMER 

OFF 

OFF 

ON 

9

 EVENT 

OFF-TIMER 

ON 

ON 

OFF 

10

 SOAK 

ON-TIMER 

OFF 

ON 

OFF 

11

 SOAK 

OFF-TIMER 

ON 

OFF 

ON 

ON = Alarm Relay energized     OFF = Alarm Relay de-energized 

Содержание 96VTR

Страница 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Страница 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Страница 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Страница 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Страница 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Страница 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Страница 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Страница 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Страница 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Страница 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Страница 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Страница 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Страница 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Страница 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Страница 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Отзывы: