Table III - Programmable Auto Tune Initialization Modes 

Setting

 

Auto Tune Initialization Modes

 

0

 

Autotune can only be initiated manually with the Setpoint (SV) not equal to the 
Process (PV) 

1

 

Autotune can only be initiated manually with the Process (PV) equal to the 
Setpoint (SV) 

2

 

Autotunes automatically when the controller is FIRST powered up if the PV < SV 

3

 

Autotunes automatically when the controller is FIRST powered up if the PV = SV 

4

 

EVERY time the controller is powered up the autotune process begins 
automatically if the PV  < SV 

5

 

EVERY time the controller is powered up the autotune process begins 
automatically if the PV  = SV 

 

9.2.2 Auto Tune Procedure 
 

Note: 

For Auto Tune to be effective, the controller must be connected in line with 

the working application. The process must be running as close to expected 
operation as possible. 

 

a. 

In order to automatically set the Tuning parameters of Level 2 which are ‘

Pb

’ 

Proportional Band, ‘

ti

’ Integral time (also known as Reset), and ‘

td

’ Derivative time 

(also known as Rate), first adjust the controller's setpoint (SV) to a value which 
closely approximates your application. 

b. 

Make sure that the value for Proportional Band (Pb) is NOT zero (zero initializes 
ON/OFF control). 

c. 

To initiate Auto Tune, press and hold the SCROLL key for at least 5 seconds until 
the 'AT" status LED lights. 

d. 

When Auto Tune is complete, the 'AT' status LED will extinguish.  The new Tuning 
values will now be stored in nonvolatile memory.  Adjustments can be made 
manually if desired in programming level 2. 

e. 

To abort an Auto Tune process, simply press and hold the RETURN key  for 5 
seconds until the 'AT' LED extinguishes. Be careful not to hold it longer than it 
takes for the 'AT' LED to extinguish otherwise you will access the MANUAL output 
control mode inadvertently. 

 

AUTO TUNE NOTE: 

The Auto Tune process can last from several minutes up to 

several hours depending upon each individual process. However, if the Auto Tune 
process does take an inordinate amount of time in a fast responding process, it is 
recommended that the Auto Tune session be aborted by powering the controller down. 
Check all physical connections as well as the controller programming to ensure that the 
controller is properly configured in the system before trying another Auto Tune session.  

 

10. AUTOMATIC AND MANUAL OUTPUT CONTROL 

AUTOMATIC CONTROL 

Automatic Control is the normal mode of controller operation and does not require 
keystrokes or special menus to access. In automatic control mode the controller 
automatically adjusts the percentage of both the Heating (Primary) and the Cooling 
(Secondary) outputs so that the PV = SV.   

 
MANUAL CONTROL 

Manual control allows the user to manually drive the Primary and Secondary output 
percentages from 0.0 through 100.0% (for testing purposes).  To use this feature you 
first have to unlock it. Press and hold the DOWN and RETURN keys until the display 
flashes. Press and hold the RETURN key for 5 seconds to access the Manual Mode. 

Содержание 96VTR

Страница 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Страница 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Страница 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Страница 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Страница 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Страница 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Страница 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Страница 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Страница 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Страница 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Страница 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Страница 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Страница 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Страница 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Страница 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Отзывы: