background image

9                                     96VTR      Ver. 2.0   11/99

 

HiLt: 

High limit (of Span or Range). Set High Limit higher than the highest expected SV 

and PV display. Note that the high limit setting is limited by the range of the type 
of input used (refer to Section 2.2 for ranges).   

9. PARAMETERS IN THE FOURTH PROGRAMMING LEVEL 

Press and hold the SCROLL and RETURN keys simultaneously for 5 seconds to enter 
this level from the previous programming level. To return to normal operation at any 
time, press the RETURN key. 
 

LoCA and HiCA: 

Low and High Input Calibration values used for engineering units 

scaling. Refer to Section 9.1 below for details.  

tunE:

 Auto-tuning ‘automatic initialization mode’ selection. Select the criteria by which 

the controller initiates an automatic Auto Tune session. Set this parameter as 
desired from the Table in Section 9.2. To activate Auto Tune manually, refer 
to Section 9.2. 

 
9.1. CALIBRATION

 

Important Note: 

Special equipment is required to perform calibrations. Do not initiate 

the calibration process unless fully prepared to do so.  
a. 

"LoCA" (Low Calibration) is the first parameter to appear in this level. 

b. 

For temperature inputs, connect a Thermocouple (mV) or RTD (resistance) 
simulator to the controller's input terminals.  For a process DC input, use a 4-20mA 
or 1-5VDC signal, depending on the input type of the controller.    

c. 

Apply the low input signal to the controller which corresponds to the range you are 
using, i.e., for 4-20 mA inputs, 4 mA would now be applied to the controller.  

d. 

Use the UP/DOWN arrow keys to set the value which will display when a 4mA 
signal is applied to the controller. For example, for a 4-20mA unit to display from –
50 to +150, set ‘LoCA” to –50. 

e. 

Press and hold the RETURN key for at least 5 seconds and the parameter on the 
display will change from "LoCA" to "HiCA" (High Calibration).  The Low Calibration 
value is now written into the controller's non-volatile memory. 

f. 

Apply the high input signal to the controller which corresponds to the range you are 
using. For example, for a 4-20mA input controller, apply a 20mA signal.  

g. 

Use the UP/DOWN arrow keys to set the value which will display when a 20mA 
signal is applied to the controller. For example, for a 4-20mA unit to display from –
50 to +150, set ‘LoCA” to +150. 

h. 

Press and hold the RETURN key for at least 5 seconds. The display will change 
from "LoCA" to "SP". The High Calibration value is now written into the controller's 
non-volatile memory. 

i. 

Input a signal midway between the Low and High Calibration signals previously 
applied (12mA in the example for a 4-20mA input) and verify that the display shows 
a value midway between the high display and the low display.  For the example 
above, for a -50 to +150 display range, a 12mA input will d50. If not, try the 
calibration procedure again. 

j. 

Press the RETURN key when complete to return to normal operation. 

 
9.2 AUTO TUNING 

 

9.2.1 Auto Tune Initialization Modes 

The Controller has the capability to start an Auto Tune session automatically. If this is 
desired, select the conditions whereby an Auto Tune session will automatically begin 
from Table III below. The controller defaults to Setting = ‘0’ (user initiates an Auto Tune 
session). To manually initiate an Auto Tune session follow the procedure in Section 
9.2.2. 
 
 

Содержание 96VTR

Страница 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Страница 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Страница 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Страница 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Страница 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Страница 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Страница 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Страница 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Страница 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Страница 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Страница 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Страница 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Страница 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Страница 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Страница 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Отзывы: