Model 48VTR 1/16 DIN Process Controller

  

 

1. INTRODUCTION 

 
The 48VTR is a microprocessor-based device which can compare a process input 
(thermocouple, RTD, or analog input) to a user-programmable setpoint and adjust the 
process (via relay or analog output), to bring the process to the desired setpoint. This Three-
Mode PID controller offers: 
 

  Simultaneous Process Value (PV) and Setpoint Value (SV) display 
  Automatic alarm functions (11 in all) 
  Auto-Tuning automatically tailors the controller's response to a specific process 
 Security 

lock-out 

  Ramp-to-Setpoint and Soak functions 
 Input 

selectability 

 

 

English / Español 

Содержание 48VTR

Страница 1: ...etpoint and adjust the process via relay or analog output to bring the process to the desired setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display...

Страница 2: ...0 x 45 0mm 0 5mm 2 2 Input Specifications Thermocouple input Programmable Types J K T E B R S N Cold Junction Compensation Thermocouple Break Protection Upscale and Downscale Lead Wire Effect 0 015 o...

Страница 3: ...nting bracket Slide meter into panel through the cutout 3 3 Replace the mounting bracket and then tighten the bracket screws Do not tighten the mounting screws excessively 3 4 Connect the power cord t...

Страница 4: ...user s requirements Error messages are also displayed on these red LED Digits Programming details and error messages are explained later in this manual 5 2 SV Setpoint Variable Display LEDs During no...

Страница 5: ...regard to input signal nnnn Under range condition with regard to input signal Input sensor not connected or is inoperable 5 4 Keypad Descriptions SCROLL Key Press once to access the programming mode...

Страница 6: ...controller will monitor the changing PV and override the controller output if necessary to limit the PV s rate of change oPoF Output Offset Manual reset function The user can program a value 0 0 to 10...

Страница 7: ...arameters adjustable Level 1 parameters A1SP only 1 Same as 0 level 1 parameters Ramp and A1SP 2 Same as 0 level 1 parameters oPoF and A1SP 3 Same as 0 level 1 parameters Ramp oPoF and A1SP 4 Same as...

Страница 8: ...larm relay outputs default in the event of controller error 0 OFF OFF 1 OFF ON 2 ON OFF 3 ON ON Addr Not used Set to 0 PVoF PV Offset Permits the user to offset the PV indication from the actual PV Fo...

Страница 9: ...ch corresponds to the range you are using i e for 4 20 mA inputs 4 mA would now be applied to the controller d Use the UP DOWN arrow keys to set the value which will display for a 4mA input For exampl...

Страница 10: ...de manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold the SCROLL key again for 5 seconds until the decimal stops flashing NOTE The Auto Tune process can l...

Страница 11: ...Set the Soak time in parameter timE in the First Programming Level The Output and Alarm Relays must be wired in series so that the Alarm relay can switch the control relay at the appropriate times ref...

Страница 12: ...e Selections for parameter A1Fu 00 Deviation High Alarm For the Deviation High Alarm the value entered for the A1SP parameter equals the amount the controller s HIGH alarm setpoint is offset from the...

Страница 13: ...er up the alarm relay energizes When the PV SV the alarm relay de energizes When the timer counts down to zero the relay energizes Set the timer at parameter time in Programming Level 1 See Table IV b...

Страница 14: ...to 0 Hysteresis is similar to deadband A region extending from the alarm setpoint up or down depending upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is...