Burst immunity test
± 2 KV DC power port
EN 61000-4-4
± 1 KV signal line
Surge immunity test
± 0,5 KV DC power port (line to earth)
EN 61000-4-5
± 0,5 KV DC power port (line to line)
± 1 KV signal line (line to earth)
Immunity to conducted disturbances
inducted by radiofrequency field
0.15 ÷ 80 MHz, 10V
EN 61000-4-6
Voltage dips, short interruptions and
voltage variations immunity test
Port: AC mains; Level:
100% duration: 1 cycle and 250 cycles (50Hz);
40% duration: 10 cycles (50Hz);
70% duration: 25 cycles (50Hz);
Phase: 0°-180°
Test executed on the 230Vac side of the Exor International Power Supply
EN 61000-4-11
Durability information
Backlight service life
40000 Hrs. or more
(LED type)
(Time of continuos operation until the brightness of the
backlight reaches 50% of the rated value when the
sorrounding air temperature is 25°C) - see Note 1
Front foil
10 years if the surrounding air temperature is 25°C
(without directly exposure to
sunlight or UV ray)
UV Resistance
Indoor applications: After 300 hours cycled humidity in
QUV accelerated weathering, some yellowing and
brittleness may be present. - see Note 2.
Touch screen reliability
> 1 milion operations
Note 1: Extended use in environments where the surrounding air temperature is 40°C or higher may degrade
backlight quality/reliability/durability.
Note 2: Solvent resistance:
Contact for 1/2 hour at 21°C, No visible effect: Acetone, Butyl Cellosolve, Cyclohexanone, Ethyl Acetate,
Hexane, Isopropyl Alcohol, MEK, Methylene Chloride, Toluene, Xylene
Contact for 24 hours at 49°C, No visible effect: Coffee, Ketchup, Lemon Juice, Mustard (slight yellow stain),
Tea, Tomato juice.