23
MANUGENETOP5xx - Version 2.00
© 2018 EXOR International S.p.A. - Subject to change without notice
Below you can find relation between modules and max number of modules that can be used into eTOP500
serie panels, based on their Interface Type:
Module
Application
Max Modules
Interface Type
Bus Extension
connector
PLCM01
CAN
1 for eTOP50x
2 for eTOP51x
CAN
Y
PLCM01-NE
CAN
1 for eTOP50x
2 for eTOP51x
CAN
N
PLCM02
KNX
1
Serial
N
PLCM03
Serial RS232
2
Serial
Y
PLCM04
Serial RS485
2
Serial
Y
PLCM05
CODESYS V2
License
1
Y
PLCM06
Profibus DP
1
SPI
N
PLIO03
Multifunction I/O
1
SPI
N
PLIO06
Compact I/O
2
SPI
N
Max modules refers to max number of modules can be plugged into the HMI (all slots),
If you are planning to use PLCM03 and PLCM04 (additional serial ports) you will obtain following “COM -
Slot#” association:
•
a module plugged in Slot#1 or into Slot#2 will be COM2,
•
a module plugged in Slot#3 or into Slot#4 will be COM3.
If you are planning to use two PLCM01 (CAN interface) you will obtain following Slot# association:
•
a module plugged in Slot#1 or into Slot#2 will be the CanPort 0,
•
a module plugged in Slot#3 or into Slot#4 will be the CanPort 1.
5 Connections