Product information
Step
Action
Illustration
2b
For steel chimneys:
Remove the lid from the power unit and mount
the bracket (optional extra) using screws and nuts.
Drill 4 mm holes in the chimney and mount the
device using selftapping screws (max. 1 m from
the chimney fan).
Note: Position the device where it has the best line
of sight to the control panel.
3
Connect the wires according to the diagram at the
bottom.
A: Supply voltage (cable with plug attached).
B: Connection to a chimney fan.
C: Building automation
D: Connection to temperature sensor.
When installing cables, wires should be used
be approx. 8 cm free of the jacket.
Note: There must be no power on
device when connecting wires.
A
C
B
4
Attaching armoured hose from chimney fan.
E: Remove the screw connector from the armoured
hose. Keep the small plastic clamping ring!
F: Fit the nut from the connector from the power
unit.
G: Fit the plastic clamping ring on the armoured
hose.
Attach the armoured hose to the power unit.
E
G
F
Wiring diagram
Brown
Blue
Chimney fan
Socket
White
Red
Power Unit
Brown
Blue
1
2
3
Supply Motor
Green/Yellow
3x1,5
3x1,5
Sensor
Nreg
L1
4
5
6
Blue
Brown
13
14
Temperature sensor
13
14
Red
White
2X0,75
Start/
Stop
7
8
9
10
11
12
0-10V
In
0-10V
Out
Note: From the temperature sensor, the two red wires in terminal 7 and the two white in terminal 8.