Troubleshooting
5.
Technical specifications
5.1. Troubleshooting
Error message Overview
Types of errors
Description
Error 1 - “No connection to Power Unit”
Power Unit and control panel are too far apart.
Error 2 - “Temperature sensor missing”
The temperature sensor is not installed correctly or is malfunctioning.
Error 3 - “Temperature above 400°C!“
The temperature is too high in the chimney.
Error 4 - ” No power to Power Unit!”
There is no power to the Power Unit.
Error 5 - ” Not enough draft in the chimney”
There are not enough draft in the chimney to make it work optimally.
Error 6 - ” Pressure sensor missing”
The pressure sensor is not installed correctly or has been lost
connection to the device.
Error 7 - “Service Switch OFF”
The service switch is off (Power failure).
Error 8 - “Low Battery!”
The battery is low on power.
Corrective Actions
If none of the following works, you can always try to restart the panel.
See how to restart the panel in section ”2.2. General use of the control panel ”on page 8.
Observation*
Action
No light in the display on the control
panel when activated
• Charge the control panel
Empty battery appears on the display
• Charge the control panel
Announcement;
"Battery low"
in a dialog
box
• Charge the control panel
No draft in the chimney, but the display
shows it is in operation
• Check if the wing of the chimney fan is rotating
• Check if the chimney is blocked
The temperature does not appear in the
display
• Check the activation of the sensor in the menu
The chimney fan does not start or stop
automatically
• Check the activation of the sensor in the menu
• Check the start and stop temperatures under the Settings menu
• Check that the sensor is positioned correctly below the fan
• Replace if the sensor, if it is necessary and defective
Announcement;
“No signal”
on the
display
• Check the control panel’s distance from the Power Unit (max. 18 m).
• Place the control panel in a more optimal location (for example, if conversion
has been made, the signal may have deteriorated).
• If a signal cannot be obtained, a repeater can be added to the network (see
section 1.2 Accessories).
Announcement;
“Warning! To high
chimney temperature”
on the display
• Excessive chimney temperature - limit the combustion.
• Check the settings for the temperature in the Settings menu
Announcement; “
No units added
” on
display
• No devices have been added to the control panel
(see section 2.10 Signal test and add / delete units).
* Note: All alarm views will disappear when the error is corrected. See the overview of troubleshooting under the Error Log menu.