12
| UK
Your energy.
Optimized.
Standard installation
The diagram shows how a separate solenoid valve (SMG) must be connected to the EFC21.
The solenoid valve is part of the separate fail-safe system and will cut off the gas supply in the case of
insufficient system chimney draught (controlled by the fan pressure switch).
•
Connect the earths of the mains supply, chimney fan and solenoidvalve together (SMG).
•
Connect the chimney fan and pressure switch to terminals 1–5.
•
Connect the SMG to terminals 6–7.
•
Connect the optional Air inlet monitoring to terminals 10–11.
If this monitoring is not mandatory, then a jumper must be fitted across terminals 10–11.
•
Connect mains supply to terminals marked ”Supply”.
Wiring diagram
Unit
Chimney fan with pressure switch (PDS)
Isolation switch
EFC21
Mains
SMG (solenoid valve)
Gas