Technical specifications
The fan will start at full speed when the EFC21 is activated. Once the system detects there is sufficient
chimney draught, the gas fireplace can be lit and the fan speed will fall to the pre-set level.
The control has a step-up function and a built-in 15 second delay to avoid inadvertent cut-outs.
If the control system is switched off the chimney fan will stop.
But an optional three-minute run on can be set by the DIP switch.
Technical data
Description
EFC21
H x W x D [mm]
85 x 126 x 32
Supply voltage
230 V ±10%/50 Hz
Fuses:
T 3,15 A
Release out
Max. 3,15 A 250 VAC/3,15 A 30 VDC
EFC21 SMG out
230 VAC, max. 100 VA
Chimney fan out
Max. 1.8 A/230 V (AC3)
Air inlet (Damper)
24 VDC (closed-circuit supply)
External start
24 VDC (closed-circuit supply)
Ingress Protection
IP 30
Material
ABS plastic
Ambient temperature:
-10 °C to + 40 °C