Commissioning

All windows and doors must be closed prior to commissioning. If there is another form of ventilation in the 

room, it should be run at full speed during the commissioning.

DIP switch

Check the factory-set DIP switch setting before commissioning (Fig. 1-J)

DIP switch

Function

Factory setting

OFF

ON

1

MANUAL RESET

ON

Automatic RESET

following power 

failure or faulty 

chimney draught

Manual RESET 

following power 

failure or faulty 

chimney draught

2

RUN-ON

AFTER

VENTILATION

OFF

No fan run-on

Fan runs on for 

three minutes

Service mode

 

• 

Open control panel.

• 

Press ON/OFF button (Fig. 1-C).

• 

If the fire has to be lit during the commissioning then wait until GREEN LED is on, but not flashing.

• 

 Press the service mode button (Fig. 1-I) on the back of the cover. 

 

Alarm LED (Fig. 1-A) will flash RED, and the operating LED (Fig. 1-B)

 

will flash according to the position of the pressure switch – see the table below.

RED

Insufficient chimney draught (C-NC)

GREEN

Sufficient chimney draught (C-NO)

YELLOW

No signal from pressure switch. Check the wiring

The service mode will deactivate automatically after 30 minutes or the next time the ON/OFF button is pressed.

Commissioning is carried out with the control box open. 

Only touch components with electrically insulated tools.

In service mode the PDS and Air inlet safety function are disabled.

Содержание EFC21

Страница 1: ...Your energy Optimized Controls EFC21 UK Read and save these instructions...

Страница 2: ......

Страница 3: ...ctrical wiring 11 Standard installation 12 Installation with external ON OFF 13 EFC21 coupled directly to a gas fireplace control 14 Commissioning 15 Service mode 15 Setting the potentiometer 16 Setti...

Страница 4: ...waste and disposed of according to national legislation to protect the environment and personnel that may come into contact with waste How to use this manual This manual has been prepared based on th...

Страница 5: ...ks a dangerous situation that in the worst case scenario can cause serious personal injury or signi cant damage to the product Electricity hazard High Voltage Marks a situation in which caution is adv...

Страница 6: ...product must be earthed Get assistance from an quali ed electrician when in doubt This product must always be disconnected under the installation Prior to servicing the product disconnect the power an...

Страница 7: ...irective 2016 426 EC and EN298 2012 Incorrect use may result in problems with soot chimney fires etc which might damage the product Please check out this site for advice about the product www exodraft...

Страница 8: ...sonnel Exodraft reserves the right to change these guidelines without prior notice The warranty and liability does not cover instances regarding personal injury or damage to property or the product th...

Страница 9: ...ent cut outs If the control system is switched off the chimney fan will stop But an optional three minute run on can be set by the DIP switch Technical data Description EFC21 H x W x D mm 85 x 126 x 3...

Страница 10: ...r inlet monitoring terminal Q External ON OFF terminal R Power supply terminal S n a Construction and components SERVICE MODE 1 2 MANUAL RESET POST PURGE Umin OFF ON 4 5 1 2 3 12 13 8 9 10 11 L N Nreg...

Страница 11: ...sides of the cover The front cover can then be tipped carefully and the frame can be fitted onto the wall The front cover is fitted with connection cable on the right side which limits how much this...

Страница 12: ...pressure switch Connect the earths of the mains supply chimney fan and solenoidvalve together SMG Connect the chimney fan and pressure switch to terminals 1 5 Connect the SMG to terminals 6 7 Connect...

Страница 13: ...s fireplace potential free switch Connect the mains earth to the earth terminal of the chimney fan Connect the chimney fan and pressure switch to terminals 1 5 Optional external ON OFF switch is conne...

Страница 14: ...ff the gas fireplace potential free switch Connect the mains earth to the earth terminal of the chimney fan Connect the chimney fan and pressure switch to terminals 1 5 Optional external ON OFF switch...

Страница 15: ...control panel Press ON OFF button Fig 1 C If the fire has to be lit during the commissioning then wait until GREEN LED is on but not flashing Press the service mode button Fig 1 I on the back of the...

Страница 16: ...o 10 Pa below the previously noted cut off value Press ON OFF button Fig 1 C Service mode is now deactivated Testing the commissioning set up Prior to the test the required speed of the fan must be de...

Страница 17: ...ety circuit Typically because the fan is restarted while it is still running Flashing GREEN The fan has started and the controller is waiting for the chimney draught ok signal Flashing YELLOW Chimney...

Страница 18: ...open 2 Check the switch and wiring 3 If the installation does not have an Air inlet check that there is a jumper across terminals 10 11 Flashing RED GREEN or YELLOW Flashing RED Service mode Press th...

Страница 19: ...ber PIN 0063 BT1395 Safety check by Gas Safe Register Gas appliances should be checked for safety once a year by a installer registered in the Gas Safe Register Details of local installers can be obta...

Страница 20: ...cts Were manufactured in conformity with the provisions of the following regulations The Supply of Machinery Safety Regulations 2008 Electrical Equipment Safety Regulations 2016 Electromagnetic Compat...

Страница 21: ...enna deklaration verensst mmer med f ljande standard er Jota t m selvitys koskee on seuraavien standardien mukainen Sem eru me talin i sta festingu Pessari eru i fullu samr mi vi eftirtalda sta la Son...

Страница 22: ......

Страница 23: ......

Страница 24: ...o exodraft no www exodraft no UK Exodraft Ltd 24 Janes Meadow Tarleton GB Preston PR4 6ND Tel 44 0 1494 465 166 Fax 44 0 1494 465 163 info exodraft co uk www exodraft co uk DE Exodraft a s Niederlassu...

Отзывы: