UK |
15
3112017_EFC21_UK
Commissioning
All windows and doors must be closed prior to commissioning. If there is another form of ventilation in the
room, it should be run at full speed during the commissioning.
DIP switch
Check the factory-set DIP switch setting before commissioning (Fig. 1-J)
DIP switch
Function
Factory setting
OFF
ON
1
MANUAL RESET
ON
Automatic RESET
following power
failure or faulty
chimney draught
Manual RESET
following power
failure or faulty
chimney draught
2
RUN-ON
AFTER
VENTILATION
OFF
No fan run-on
Fan runs on for
three minutes
Service mode
•
Open control panel.
•
Press ON/OFF button (Fig. 1-C).
•
If the fire has to be lit during the commissioning then wait until GREEN LED is on, but not flashing.
•
Press the service mode button (Fig. 1-I) on the back of the cover.
Alarm LED (Fig. 1-A) will flash RED, and the operating LED (Fig. 1-B)
will flash according to the position of the pressure switch – see the table below.
RED
Insufficient chimney draught (C-NC)
GREEN
Sufficient chimney draught (C-NO)
YELLOW
No signal from pressure switch. Check the wiring
The service mode will deactivate automatically after 30 minutes or the next time the ON/OFF button is pressed.
Commissioning is carried out with the control box open.
Only touch components with electrically insulated tools.
In service mode the PDS and Air inlet safety function are disabled.