Connection of frequency converter/MPR relay
This example shows which inputs/outputs on the EBC22 need to be connected to the frequency conver
-
ter/MPR relay
•
Connect the supply voltage to terminals 1–3.
•
Loop terminals 12 & 20.
•
Connection to the boiler:
•
Connect the burner start signal to terminals 13 & 14.
•
Connect the potential free contact to terminals 11 & 19.
•
Frequency converter:
•
Connect terminals 7 & 8 to the start/stop input on the frequency converter.
•
Connect terminals 21 & 22 to the frequency converter input for external speed regulation.
•
Connect the pressure transducer (XTP) to terminals 23–28.