UK |
15
3112015_EBC22_UK
Light emitting diodes and terminal board
The chart below lists the connection options for the terminal boards and explains the various colours of the
light emitting diodes
No.
Designation
Max. load
Meaning when the light diode is …
1, 2 & 3
SUPPLY IN
230-240 V AC +/- 10 %
green: the EBC22 is connected to a power supply
4, 5 & 6
FAN OUT
3 A
green: the triac output is active
7 & 8
VFD OUT
250 V AC, 8 A, AC 3
green: the relay is connected
9 & 10
ALARM OUT
250 V AC, 8 A, AC 3
red: the relay is open
11 & 12
BOILER 1 IN
18 - 230 V DC / V AC
green: the input is active
13 & 14
BURNER 1 OUT
250 VAC, 4 A, A C 3
green: the relay is connected
15 & 16
BOILER 2 IN
18 V DC/230 V AC
green: the input is active
17 & 18
BURNER 2 OUT
250 V AC, 4 A, AC 3
green: the relay is connected
19 & 20
24 VDC OUT
100 mA
green: power supply OK
red: overload
21 & 22
0 - 10 V OUT*
20 mA
green: the output is active
23, 24 & 25
XTP IN
green: XTP connected
red: return voltage >12 V DC
26, 27 & 28
PDS IN **
green: C & NO are connected
29, 30 & 31
TEMP IN
green: temperature sensor connected
* Cable length between 0-10 V output (terminal 21 & 22) must not exceed 100 m and must be of a shielded cable 3 x 0,75 mm2.
** Terminals 26, 27 & 28 can however also be used for connecting other auxiliary surveillance equipment.