Service menu
Heating
Description
Shown for the water
heating coil 2
Forced control of water heating coil 2
Forced operation is only possible once the unit has
started.
● Set forced operation setpoint [%]
● Current input air temperature [°C]
● Set remaining time until forced operation termi-
nates [hh:mm:ss]
● Activate forced operation: On/ Off
● Current signal at heat output [V]
● Current status Heat relay 21: Open/closed
Shown for the water
heating coil 2
Set pump operation
Pump operation can be set to:
● Constant operation
● Auto
● Outdoor air temperature
● Heating requirement
Start
appears when pump is in operation.
Shown at Water heat-
ing coil 2 and if
out-
door temperature
is
selected
Set pump 2 start temperature
● The pump starts when the outdoor temperature is
lower than the set value. [°C]
Start
appears when pump is in operation.
Shown at Water heat-
ing coil 2 and if
out-
door temperature
is
selected
Set pump 2 start temperature
● The pump starts when the outdoor temperature is
lower than the set value. [%]
Start
appears when pump is in operation.
Shown for the water
heating coil 2
Setting of frost protection in water heating coil 2
● Set temperature for full frost protection [°C]
● Set temperature for frost alarm [°C]
● Set frost protection P-band [°C]
● Set heat boost upon start-up [%]
● Set Water heating coil temperature to standby [°C]
● Current water temperature [°C]
3005858-2017-09-28
Service level
34/52