Alarm no
Alarm type
Alarm delay secs
Alarm limit
Auto reset
Machine stop
Alarm text - Handheld terminal
84
B
3
N/A
Cooling error 2: Compressor 2 overheated circuit 1
85
B
3
N/A
Low cooling pressure circuit 2
86
B
3
N/A
High cooling pressure circuit 2
87
B
3
N/A
Cooling error 3: Compressor 1 overheated circuit 2
88
B
3
N/A
Cooling error 4: Compressor 2 overheated circuit 2
90
B
3
N/A
Pressure transmitter error: DX low pressure 1
91
B
3
N/A
Pressure transmitter error: DX high pressure 1
92
B
3
N/A
Pressure transmitter error: DX low pressure 2
93
B
3
N/A
Pressure transmitter error: DX high pressure 2
94
B
3
N/A
X
VOC/CO2 sensor not configured
95
B
3
N/A
X
FanOpt. supply air not configured
96
B
3
N/A
X
FanOpt. extract air not configured
100
A
3
N/A
X
X
Pressure transmitter 0 (PTH6202): No communication
101
A
3
N/A
X
X
Pressure transmitter 1 (PTH6202): No communication
103
A
3
N/A
X
X
Pressure transmitter 3 (PTH6202): No communication
104
A
3
N/A
X
X
Pressure transmitter 4 (PTH6202): No communication
105
A
3
N/A
X
X
Pressure transmitter 5 (PTH6202): No communication
106
A
3
N/A
X
X
Pressure transmitter 6 (PTH6202): No communication
107
A
3
N/A
X
X
Pressure transmitter 7 (PTH6202): No communication
108
A
3
N/A
X
Expansion module45 1 (Air2Ext45): No communication
109
A
3
N/A
X
Expansion module45 2 (Air2Ext45): No communication
111
B
3
N/A
X
Pressure transmitter, supply air (PTH6202): No communication
112
B
3
N/A
X
Pressure transmitter, extract air (PTH6202): No communication
113
B
10
N/A
X
VOC/CO2 sensor error: VOC/CO2 sensor disconnected/short-
circuited
115
A
3
N/A
X
Supply air EC controller: Alarm stop
116
A
3
N/A
X
Supply air EC controller: Rotor blocked
117
B
3
N/A
Supply air EC controller: Power restriction
118
B
3
N/A
Supply air EC controller: Low supply voltage (Vlo)
119
B
3
N/A
Supply air EC controller: High supply voltage (Vhi)
120
B
3
N/A
Supply air EC controller: High temperature (Thi)
121
B
3
N/A
Supply air EC controller: High internal ripple voltage
122
A
3
N/A
X
Extract air EC Contrl. Alarm stop
123
A
3
N/A
X
Extract air EC Contrl. Rotor blocked
124
B
3
N/A
Extract air EC Contrl. Power restriction active
125
B
3
N/A
Extract air EC Contrl. Low supply voltage (Vlo)
126
B
3
N/A
Extract air EC Contrl. High supply voltage (Vhi)
127
B
3
N/A
Extract air EC Contrl. High temperature (Thi)
128
B
3
N/A
Extract air EC Contrl. High internal ripple voltage
3005858-2017-09-28