Service menu
Heating recovery
Description
Shown for tempera-
ture-controlled ice pro-
tection
Settings for pressure-controlled de-icing, time
● De-icing type: Static/Dynamic
● Start measurements: Yes/No
● De-icing time [s]
● Remaining de-icing time [s]
● Measurement status
Shown for tempera-
ture-controlled ice pro-
tection
Settings for pressure-controlled de-icing, pressure
● Current crossflow heat exchanger pressure [Pa]
● De-icing pressure, static [Pa]
● De-icing pressure, dynamic [Pa]
● De-icing pressure, current [Pa]
Gain factor
● Set gain factor
Rotary heat exchanger
Shows current status of rotary heat exchanger
● Current outdoor temperature [°C]
● Current exhaust air temperature [°C]
● Current recovery signal [%]
● Current extract air temperature [°C]
● Current supply air temperature [°C]
Forced control of rotary heat exchanger
Forced operation is only possible once the unit has
started.
● Setting of remaining time until forced control ex-
pires: [hh:mm: ss]
● Activate forced control: On/ Off
● Set forced operation setpoint for motor [%]
● Current extract air temperature [°C]
● Current supply air temperature [°C]
Efficiency
● Correction factor [%]
● Alarm type: A or B
● Alarm in case of low efficiency: Select/deselect
● Alarm level [%]
● Current efficiency [%]
Only relevant if pres-
sure inlet:
Rot. heat
exchanger (outdoor/
supply air)
is config-
ured
Measure pressure reference
● Measure pressure reference: Select/deselect
● Measurement status
● Current pressure over rotor* [Pa]
*Pressure over the rotor's supply air string
Only relevant if pres-
sure inlet:
Rot. heat
exchanger, de-icing
(exhaust air/extract
air)
is configured
Dynamic de-icing
● Measure pressure reference, de-icing: Select/dese-
lect
● Measurement status: Not measured/measured
● Current pressure over rotor [Pa]
● Estimate pressure limit, de-icing* [Pa]
*Pressure over the rotor's extract air string
3005858-2017-09-28
Service level
36/52