3.1.8 Store functions
Installer menu
Store functions
Description
SHOP FUNCTIONS
Select on and off settings for energy saving functions.
This menu is only available if, under
EXcon modules >
configure > SettingsShop functions
is crossed off.
Submenu
Submenu
Setting of functions in fan
Set speed change for fans
● None
● Change Low Low > High
● Change High > Low
Set heating 2
Choose whether activation of
Heat2
is to override fan
speed.
● Set fan speed change in case of active
Heat2
.
Set functions in recirculation damper
Set blocking of Heat2 with recirculation air
● Mark to activate blocking
Heat 2
is blocked when the unit runs with air recircula-
tion.
Set heating with recirculation air
● Mark to activate the function
● Set heating time [Sec]
● Read off current start-up time [s]
● Set outdoor temperature for activation [˚C]
When the function is activated, the unit will operate with
recirculation during the early morning heating of the
shop if the outdoor temperature is above the set value.
Set function for Heat 1
Heating surface 1
can be set according to various reg-
ulation principles.
Set min return water limits
● Mark to activate the function
● Set min. return temperature in
Heat 1
[˚C]
● Set time delay for
heat 1
[Sec]
● Read off current blocking time [s]
3005858-2017-09-28